Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
5. CONNECTIONS
NOTE!
Before carrying out any operations on the unit read the 'Safety standards' chapter carefully.
WARNING!
Battery power terminals can be supplied by:
- external battery cabinet;
- internal battery modules;
- UPS power modules.
Before working on this circuit ensure that:
- all the external battery cabinet switches are in OFF position;
- all the internal battery modules are disconnected;
- the UPS is in maintenance bypass mode (refer to 'Operating modes' chapter);
- all UPS power modules are disconnected;
Check the presence of voltage before operating.
WARNING!
The unit is supplied with the bars already installed. In the case of separate mains connection
remove the bars.
FLOOR MOUNTING ANTI-INTRUSION INSTALLATION KIT
A
B
C
NOTE!
The cables coming from the rear of the unit must pass
through the appropriate gap.
This operation must be carried out:
- before wiring operations;
- before securing the kit to the unit and the floor.