Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
13. TECHNICAL SPECIFICATIONS
Number of modules
1
2
3
4
5
Power
kW
25
50
75
100
100
Power
kVA
25
50
75
100
100
Input
Input mains voltage
3ph 480 V (+15/-15%) up to -40% @ 50% of nominal load
Input mains frequency
Hz
60 +/-10%
Input power factor
≥
0.99
(1)
Total harmonic input current distor-
tion (THDi)
≤
3% (@: Pn, Resistive load, Mains THDv
≤
1%)
Output
Output voltage (three phase)
V
480
Frequency
Hz
60
Total output voltage distortion
(THDv)
%
≤
1% (@ Pn, Resistive load)
Overload
(2)
%
125% for 10 minutes, 150% for 1 minute
Overload
(2)
10 min
kW
125
1 min
kW
150
Crest Factor
≥
2.7
≥
3.3
Bypass
Bypass input voltage
V
Nominal output voltage ±15%
Bypass input frequency
Hz
60 +/-2% selectable (±8% if GENSET is used)
Stored energy mode of operation
Number of battery blocks (VRLA)
From 18+18 to 24+24
Environmental
Operating temperature
°F / °C
32 to 104 °F / 0 to +40 °C
(3)(4)
Storage temperature
°F / °C
23 to 122 °F / -5 to +50 °C
Relative humidity
%
95% condensation-free
Altitude (max)
ft
3280 ( 9840 with derating)
Acoustic noise at 1m
dBA
≤
58
Required air capacity
CFM
1178
Dissipated power (max)
W
5200 @ Pn (3000 @ 56 kW)
Dissipated power (max)
BTU/h
17750 @ Pn (10250 @ 56 kW)
Dimensions and Weight
Dimensions (W x D x H)
ft / mm
1.97 x 2.92 x 6.48 ft. / 600 x 890 x 1975 mm
Empty cabinet
lbs / kg
1043 lbs / 473 kg
UPS module
lbs / kg
75 lbs / 34 kg
Bypass module
lbs / kg
55 lbs / 25 kg
Battery module
lbs / kg
-
5
Standard
Safety
UL1778 CSA C22.2 N. 107.3-05
EMC
FCC part15 Class A
Performance
IEC 62040-3 (VFI-SS-111)
Degree of protection standard
NEMA 1 (IP20)
SEISMIC
OSHPD Pre-approval (optional)
1. Pout
≥
50% Sn.
2. Initial Condition Pout
≤
80% Pn.
3. For best battery lifetime the suggested temperature range
is 59 °F ÷ 77 °F.
4. According to IEC62040-3.
5. Modular battery cabinet.