56
EN
DIRIS B-10L - 551174A - SOCOMEC
Load curves – Load 3
The following Modbus table can be used only if one of the following profiles is selected:
•
Profile 7 (Multi-load Load curves)
Dec address Hex address
Words
count
Description
Unit
Data type
Function
Profil
16512
0x4080
1
Load status
0: Disabled
1: Enabled
-
U16
READ
6/7
16513
0x4081
2
Date (last point)
s
DATETIME
READ
6/7
16515
0x4083
2
Total Positive Active Power - last point
W
U32
READ
6/7
16517
0x4085
2
Total Negative Active Power - last point
W
U32
READ
6
16519
0x4087
2
Total Positive Reactive Power - last point
var
U32
READ
6
16521
0x4089
2
Total Negative Reactive Power - last point
var
U32
READ
6
16523
0x408B
1
Flag - last point
0 : Complete period - date configured
1 : Incomplete period - date not configured
2 : Complete period - date configured
3 : Incomplete period - date not configured
-
U16
READ
6/7
16524
0x408C
2
Date (previous point)
s
DATETIME
READ
6/7
16526
0x408E
2
Total Positive Active Power - previous point
W
U32
READ
6/7
16528
0x4090
2
Total Negative Active Power - previous point
W
U32
READ
6
16530
0x4092
2
Total Positive Reactive Power - previous point
var
U32
READ
6
16532
0x4094
2
Total Negative Reactive Power - previous
point
var
U32
READ
6
16534
0x4096
1
Flag - previous point
0 : Complete period - date configured
1 : Incomplete period - date not configured
2 : Complete period - date configured
3 : Incomplete period - date not configured
-
U16
READ
6/7