51
EN
DIRIS B-10L - 551174A - SOCOMEC
Average measurements – Load 1
The following Modbus table can be used only if one of the following profiles is selected:
•
Profile 4 (Single-load Monitoring)
•
Profile 5 (Multi-load Monitoring)
Dec address
Hex address
Words
count
Description
Unit
Data type
Function
Profil
8192
0x2000
1
Load status
0 : Disabled
1 : Enabled
-
U16
READ
4/5
8193
0x2001
2
Date of last instance
s
DATETIME
READ
4/5
8195
0x2003
2
Average Total Active Power
W
S32
READ
4/5
8197
0x2005
2
Average Total Reactive Power
var
S32
READ
4/5
8199
0x2007
2
Average Total Apparent Power
VA
S32
READ
4
8201
0x2009
1
Average Total Power Factor
-
S16
READ
4
8202
0x200A
1
Average Power Factor Type
0 : N/A
1 : Lagging
2 : Leading
-
U16
READ
4
8203
0x200B
2
Average Current phase 1
mA
S32
READ
4
8205
0x200D
2
Average Current phase 2
mA
S32
READ
4
8207
0x200F
2
Average Current phase 3
mA
S32
READ
4
8209
0x2011
2
Average Frequency
mHz
S32
READ
4
Average measurements – Load 2
The following Modbus table can be used only if one of the following profiles is selected:
•
Profile 5 (Multi-load Monitoring)
Dec address
Hex address
Words
count
Description
Unit
Data type
Function
Profil
8256
0x2040
1
Load status
0 : Disabled
1 : Enabled
-
U16
READ
4/5
8257
0x2041
2
Date of last instance
s
DATETIME
READ
4/5
8259
0x2043
2
Average Total Active Power
W
S32
READ
4/5
8261
0x2045
2
Average Total Reactive Power
var
S32
READ
4/5
8263
0x2047
2
Average Total Apparent Power
VA
S32
READ
4
8265
0x2049
1
Average Total Power Factor
-
S16
READ
4
8266
0x204A
1
Average Power Factor Type
0 : N/A
1 : Lagging
2 : Leading
-
U16
READ
4
8267
0x204B
2
Average Current phase 1
mA
S32
READ
4
8269
0x204D
2
Average Current phase 2
mA
S32
READ
4
8271
0x204F
2
Average Current phase 3
mA
S32
READ
4
8273
0x2051
2
Average Frequency
mHz
S32
READ
4