DIRIS B-10L - 551174A - SOCOMEC
Average measurements – Load 3
The following Modbus table can be used only if one of the following profiles is selected:
•
Profile 5 (Multi-load Monitoring)
Dec address
Hex address
Words
count
Description
Unit
Data type
Function
Profil
8320
0x2080
1
Load status
0 : Disabled
1 : Enabled
-
U16
READ
4/5
8321
0x2081
2
Date of last instance
s
DATETIME
READ
4/5
8323
0x2083
2
Average Total Active Power
W
S32
READ
4/5
8325
0x2085
2
Average Total Reactive Power
var
S32
READ
4/5
8327
0x2087
2
Average Total Apparent Power
VA
S32
READ
4
8329
0x2089
1
Average Total Power Factor
-
S16
READ
4
8330
0x208A
1
Average Power Factor Type
0 : N/A
1 : Lagging
2 : Leading
-
U16
READ
4
8331
0x208B
2
Average Current phase 1
mA
S32
READ
4
8333
0x208D
2
Average Current phase 2
mA
S32
READ
4
8335
0x208F
2
Average Current phase 3
mA
S32
READ
4
8337
0x2091
2
Average Frequency
mHz
S32
READ
4
Average measurements – Load 4
The following Modbus table can be used only if one of the following profiles is selected:
•
Profile 5 (Multi-load Monitoring)
Dec address
Hex address
Words
count
Description
Unit
Data type
Function
Profil
8384
0x20C0
1
Load status
0 : Disabled
1 : Enabled
-
U16
READ
4/5
8385
0x20C1
2
Date of last instance
s
DATETIME
READ
4/5
8387
0x20C3
2
Average Total Active Power
W
S32
READ
4/5
8389
0x20C5
2
Average Total Reactive Power
var
S32
READ
4/5
8391
0x20C7
2
Average Total Apparent Power
VA
S32
READ
4
8393
0x20C9
1
Average Total Power Factor
-
S16
READ
4
8394
0x20CA
1
Average Power Factor Type
0 : N/A
1 : Lagging
2 : Leading
-
U16
READ
4
8395
0x20CB
2
Average Current phase 1
mA
S32
READ
4
8397
0x20CD
2
Average Current phase 2
mA
S32
READ
4
8399
0x20CF
2
Average Current phase 3
mA
S32
READ
4
8401
0x20D1
2
Average Frequency
mHz
S32
READ
4