65
EN
DIRIS B-10L - 551174A - SOCOMEC
10.3. Protection alarms
The DIRIS B-10L includes 6 protection alarms alerting the user of an event on a protective device.
Make sure you have configured the protective device type used in the “Protection” menu in order to use the Protection alarms
Protection alarms can be configured in case of:
- An opening of the protective device.
- A trip of the protective device (only available for circuit breakers).
- A defect of the protective device: if one pole is in a different position from the other poles (abnormal for a multi-phase
protective device).
A time delay at the start and end of the alarm can be set for each alarm.
A digital output can be associated to each alarm to report the alarm on an output.
10.4. Logical alarms
Up to 4 "Logical alarms" can be configured to alert upon the change of status of a digital input.
A time delay at the start and end of the alarm can be set for each logical alarm.
A digital output can be associated to each logical alarm to report the alarm on an output.