GT INSTALLATION AND OPERATION INSTRUCTIONS
Page 24
Figure 35 - Conventional Mode Operation Chart
T-C & A-C Open
T-C Closed & A-C open
T-C Closed & A-C Close
T-C Open & A-C Closed
Condition
Standby
Heating Only
Domestic Only
Domestic Only
Set Point
—
HI
L0
L0
Burner On
—
HI - DIF
LO-10
LO-10
Burner Off
—
HI + 10
200°F
200°F
Heat Circ.
Off
On
Off
Off
Aux. Circ.
Off
Off
On
On
SENTRY 2100T CONTROLLER
The Sentry 2100T controller is the central controller for
the GT boiler. The Sentry handles all of the combustion
logic, along with the energy management functions.
The Sentry 2100T operates in two different modes,
Conventional or Reset, see Figures 35 & 36. The mode is
automatically determined by the presence of the outdoor
sensor. When the Sentry 2100T detects the presence of
the outdoor sensor the controller will operate in the Reset
Mode. If the outdoor sensor is not installed, the controller
will operate in the Conventional Mode.
NOTE: If the outdoor sensor is connected after the
boiler has been started power to the boiler must be
shut off and then turned back on.
Boiler Modulation
The GT boiler employs a pneumatic modulation sys-tem.
This modulation system increases or decreases the
speed of the blower to meet the heating demand. The
gas valve pressure regulator senses the air pressure
and adjusts the gas fl ow to ensure correct combustion.
The term “Set Point” is used to indicate the desired
temperature that the GT will maintain by increasing or
decreasing the input.
Indirect Water Heaters
The Sentry 2100 comes with an input and output for
a 120-volt indirect pump. When the A and C terminals
are closed, dry contact, the boiler will go immediately
to indirect domestic mode, whereby the indirect pump
is activated, and the boiler will modulate to the LO
setpoint.
Sentry Display
The Sentry 2100T contains four green lights that illuminate
to indicate the boilers state of operation, Figure 37.
Figure 37 - 2100T Display Screen
Burner/Bruleur
- Indicates that the ignition system is
activated.
Circ.
- Indicates that the heating pump is energized.
Circ. Aux.
- Indicates a call for DHW, and Indirect pump
or 3-way valve is activated.
Thermostat Demand
- Indicates that terminals T-C are
closed, iniating a call for heat.
The LED screen will display one of four values. A light will
illuminate above the function to indicate what information
is being displayed.
Water Temp
- indicates that the display is showing the
boiler water temperature.
Air
- when the outdoor air sensor is being used indicates
that the display is showing the outdoor air temperature.
Gas Input Value
- indicates the current input level. Figure
38 must be used to determine the actual input.
DHW Temp.
- indicates that there is a call for domestic
hot water.
Figure 36 - Reset Mode Operation Chart
T-C & A-C Open
T-C Closed & A-C open
T-C Closed & A-C Close
T-C Open & A-C Closed
Condition
Standby
Heating Only
Domestic Only
Domestic Only
Set Point
—
HI
Calc.
L0
L0
Burner On
—
HI
Calc
- DIF
LO-10
LO-10
Burner Off
—
HI
Calc
+ 10
200°F
200°F
Heat Circ. (C1)
Off
On
Off
Off
Aux. Circ. (Ap)
Off
Off
On
On
Summary of Contents for GT-150
Page 19: ...GT INSTALLATION AND OPERATION INSTRUCTIONS Page 19 Figure 30 Multiple 4 Wire Zone Valves...
Page 22: ...GT INSTALLATION AND OPERATION INSTRUCTIONS Page 22 Figure 33 Boiler Ladder Diagram...
Page 23: ...GT INSTALLATION AND OPERATION INSTRUCTIONS Page 23 Figure 34 Boiler Connection Diagram...
Page 40: ...WESTCAST INC 260 NORTH ELM STREET WESTFIELD MA 01085 TEL 413 562 9631 FAX 413 562 3799...