GT INSTALLATION AND OPERATION INSTRUCTIONS
Page 21
Multiple Zone Pump Controller
Models Taco SR504, Argo ARM 861 Series
Figure 32 shows the basic multiple zoned system using
circulating pumps. This wiring system is used with the
piping as shown in Figures 25.
When there is a call for heat the room thermostat
closes the circuit between the TT terminals on the pump
controller. The controller energizes the appropriate
circulating pump and closes the circuit between terminals
T and C on the Sentry 2100 control. The Sentry 2100,
provides power to the primary pump via terminal C1.
Once these pumps are on, the burner fi res.
Once the room thermostat is satisfi ed, it breaks power
to the TT terminal of the pump controller de-energizing
the XX contacts. The circuit between terminals T and C
opens shutting down the pumps and the burner.
Figure 32 - Multiple Zone Pump Controller, Models Taco SR504, Argo ARM 861 Series
Summary of Contents for GT-150
Page 19: ...GT INSTALLATION AND OPERATION INSTRUCTIONS Page 19 Figure 30 Multiple 4 Wire Zone Valves...
Page 22: ...GT INSTALLATION AND OPERATION INSTRUCTIONS Page 22 Figure 33 Boiler Ladder Diagram...
Page 23: ...GT INSTALLATION AND OPERATION INSTRUCTIONS Page 23 Figure 34 Boiler Connection Diagram...
Page 40: ...WESTCAST INC 260 NORTH ELM STREET WESTFIELD MA 01085 TEL 413 562 9631 FAX 413 562 3799...