background image

GT INSTALLATION AND OPERATION INSTRUCTIONS

Page 2

CONTENTS

Before You Start .................................................  page 2
Boiler Ratings & Capacities  ............................... page 2
Boiler Location  ................................................... page 3
Clearances to Combustible Construction  .......... page 3
Combustion Air  .................................................. page 4
General Venting Guidelines  ............................... page 4 
Horizontal Direct Vent Systems  ......................... page 5
Vertical Direct Vent Systems ............................... page 9
Condensate Drain  ............................................ page 10
General Plumbing Guidelines  .......................... page 11
Primary Loop Plumbing  ................................... page 12
Multiple Boiler Primary Loop Plumbing  ........... page 12
Secondary Loop Plumbing  .............................. page 12
Gas Supply Piping  ........................................... page 16
Electrical Wiring ...............................................  page 17
Sentry 2100 Controller  .................................... page 24
Boiler Set Up  ................................................... page 27
Boiler Operation  ............................................... page 27
Operating Instructions  ..................................... page 29
Boiler Checking & Adjusting  ............................ page 30
Gas Pressure Adjustment  ................................ page 30
Boiler Maintenance  .......................................... page 30
Wall Hung Conversion  ..................................... page 32
Trouble Shooting   ............................................. page 33
Replacement Parts  .......................................... page 38

BEFORE YOU  START

WARNING: This manual must be read and 
fully understood before installing, operation 
or servicing this boiler! Failure to follow these 
instructions could result in a fi re or explosion 
causing extensive property damage, personal 
injury or death!

These instructions cover the GT Series gas fi red, direct 
vent, low pressure, hot water boiler. GT boilers have been 
design certifi ed by CSA for use with natural and propane 
gas under the latest edition of ANSI-Z21.13/CSA 4.9, 
Gas-Fired Low Pressure Steam and Hot Water Boilers.

Each unit has been constructed and hydrostatically 
tested for a maximum working pressure of 

30 psi

207 kPa

. The GT-200 has been tested in accordance 

with Section IV of the ASME Boiler and Pressure Vessel 
Code.  Each boiler has been equipped with a 

30 psi

207 kPa 

pressure relief valve.

This manual covers the application, installation, operation 
and maintenance of a GT Series low pressure hot water 
boiler.

To obtain the safe, dependable, efficient operation 
and long life for which this boiler was designed, these 
instructions must be read, understood and followed.

Direct all questions to your Smith distributor or to the 
Customer Service Department, 260 North Elm Street, 
Westfi eld, MA 01085. Always include the model and serial 
numbers from the rating plate of the boiler in question.

The owner should maintain a record of all service work 
performed with the date and a description of the work 
done. Include the name of the service organization for 
future reference.

Where required by the authority having jurisdiction, the 
installation must conform to the Standard for Controls 
and Safety Devices for Automatically Fired Boilers, 
ANSI/ASME CSD-1.

The installation must conform to the requirements of the 
authority having jurisdiction or, in the absence of such 
requirements, to the National Fuel Gas Code, ANSI 
Z223.1-latest revision. In Canada, the installation must 
be in accordance with the requirements of CSA B149.1 
or B149.2 Installation Code for Gas Burning Appliances 
and Equipment.

If installed in the Commonwealth of Massachusetts, you 
MUST FOLLOW the additional instructions contained in 
Smith’s instruction sheet MA IOM. If you don’t have a 
copy call your Smith distributor or Smith.

BOILER RATINGS & CAPACITIES

Before undertaking the installation of the GT check the 
boiler rating plate to ensure that the boiler is the proper 
size for the job. 

Also ensure that the boiler has been set up for the type 
of gas available at the installation site. Other important 
considerations are the availability of an adequate 
electrical supply, fresh air for combustion and proximity 
a suitable outside wall.

High Altitude Operation

The GT boiler is designed to operate to capacity in 
installations with 

2000 ft

610 m

 of elevation or less. At 

elevations higher than 

2000 ft

610 m

 the unit will de-rate 

due to the lower air density, see Figure 1.

NOTE: It is the 

Installers responsibility

 to check 

the combustion, and to adjust the combustion in 
accordance to Operating Instructions Section.

Summary of Contents for GT-150

Page 1: ...NING If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life INSTALLER THESE INSTRUCTIONS MUST BE AFFIXED ADJAC...

Page 2: ...d long life for which this boiler was designed these instructions must be read understood and followed Direct all questions to your Smith distributor or to the Customer Service Department 260 North El...

Page 3: ...however 24 in 610 mm is recommended 2 An optimum site will be level central to the hot water piping system and close to an outside wall NOTE This boiler is designed for direct placement on a combustib...

Page 4: ...let System Attachment One of the following materials is to be used for the air intake pipe 3 in 76 mm ABS 3 in 76 mm PVC Sch 40 pipe 3 in 76 mm Galvanized Steel pipe See Table 2 for the maximum equiva...

Page 5: ...mm vent collar to 3 in 76 mm at the boiler Figure 3 Figure 3 Vent Pipe To Boiler Attachment The maximum combined equivalent vent and intake pipe lengths are listed in Table 2 The length specified is t...

Page 6: ...liance will produce a plume of water vapor and should be taken into consideration when selecting an adequate vent terminal location A 3 ft 0 9 m diameter stainless plastic or vinyl shield can be used...

Page 7: ...lations that have to exit the foundation below grade excavate the site as shown in Figure 8 to a point below where the pipes exit the building Maintain the proper vent clearances as outlined above Att...

Page 8: ...ditions must apply 1 If limited to two terminals the horizontal centerline distance must be 4 in 102 mm or greater than 24 in 610 mm to prevent flue gas recirculation For more than two terminals locat...

Page 9: ...terminal must always be a minimum of 12 in 305 mm plus the snow allowance above any surface that will support snow however a snow allowance of 24 in 610 mm is highly recommended Figures 15 16 Consult...

Page 10: ...nsure that the air inlet and vent system lengths are within the maximums specified in Table 2 The debris screens provided with the boiler must be installed in both the air intake and vent terminals In...

Page 11: ...e products such as Fernox Superfloc for new installations and CHR Central Heating Restorer for retrofits Also add an inhibitor to the system water to prevent limestone and magnetite deposits from form...

Page 12: ...diagram to be used as a vacuum breaker and to eliminate air upon filling Figure 21 LWCO Air Vent Piping PRIMARY LOOP PLUMBING This low mass boiler requires a continuous minimum water flow for proper...

Page 13: ...terminals C1 L2 5 See Table 3 for Indirect Water Heater pump flow requirements This pump is wired to terminals AP L2 6 Set pressure reducing valve to 12 psi 83 kPa 7 Use 30 psi 207 kPa relief valve ma...

Page 14: ...nals C1 L2 5 See Table 3 for Indirect Water Heater pump flow requirements This pump is wired to terminals AP L2 6 Set pressure reducing valve to 12 psi 83 kPa 7 Use 30 psi 207 kPa relief valve max Loc...

Page 15: ...tiple Zones Using Pumps Figure 26 Secondary Loop For Multiple Zones Using A Bypass Valve Note Velocity noise may be a problem when the entire output of the system pump is flowing through the zone with...

Page 16: ...he gas valve which can cause a fire or explosion GAS SUPPLY PIPING The GX hot water boiler comes from the factory ready to be piped to the gas supply The National Fuel Gas Code ANSI Z223 1 NFPA 54 and...

Page 17: ...ps with a maximum inrush of 6 amps If the amp draw of the pumps exceeds these maximums a pump controller or isolation relay must be used to prevent damage to the boiler Damage caused by improper wirin...

Page 18: ...uit between terminals T and C shutting down the pumps and the burner Multiple Zones w Taco Valve Controller Models ZVC403 to ZVC 406 Figure 31 shows the basic multiple zoned system using normally clos...

Page 19: ...GT INSTALLATION AND OPERATION INSTRUCTIONS Page 19 Figure 30 Multiple 4 Wire Zone Valves...

Page 20: ...GT INSTALLATION AND OPERATION INSTRUCTIONS Page 20 Figure 31 Multiple Zones w Taco Valve Controller Models ZVC403 to ZVC 406...

Page 21: ...on the pump controller The controller energizes the appropriate circulating pump and closes the circuit between terminals T and C on the Sentry 2100 control The Sentry 2100 provides power to the prima...

Page 22: ...GT INSTALLATION AND OPERATION INSTRUCTIONS Page 22 Figure 33 Boiler Ladder Diagram...

Page 23: ...GT INSTALLATION AND OPERATION INSTRUCTIONS Page 23 Figure 34 Boiler Connection Diagram...

Page 24: ...GT will maintain by increasing or decreasing the input Indirect Water Heaters The Sentry 2100 comes with an input and output for a 120 volt indirect pump When the A and C terminals are closed dry cont...

Page 25: ...ter Error Code On Off NOTE LFS must not be set below 48 on the GT150 model To start the control operation return to RUN on the menu and press Function Normal operation will begin Recommended Settings...

Page 26: ...C 70 F 21 C 1 85 RESET TEMPERATURE HICalc RES Outdoor Air x Reset Ratio RES 70 F 21 C 32 F 0 C x 1 85 70 F 21 C 70 6 F 21 C 70 F 21 C 140 6 F 42 C NOTE The design temperature is 0 F 18 C outside air...

Page 27: ...mmediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control that has been under water NOTE The GT was tested with Natural...

Page 28: ...ystem by turning the thermostat to it s lowest setting and then back to where it was or by momentarily interrupting the electrical power to the boiler D With the burner in operation close the manual s...

Page 29: ...r Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control that has been under water 1 STOP Read the safety informatio...

Page 30: ...s up to 2000 ft 610 m At elevations above 2000 ft 610 m input ratings should be reduced by 4 for each 1000 ft 305 m above sea level Check the input rate as follows NATURAL GAS 1 Turn off all other gas...

Page 31: ...ing at the valve Figure 2 6 Remove the nuts used to attach the burner to the heat exchanger 7 Carefully slide the burner out of the unit 8 Inspect the burner for damage or signs of deterioration Use a...

Page 32: ...bolts 7 Once the unit is level install the bottom two 14 3 lag bolts 8 Remove the Air Inlet Pipe assembly and Metering elbow from the gas valve venturi assembly Figure 44 Figure 44 Air Inlet Pipe Remo...

Page 33: ...calculated using formula in Section 8 1 If the thermostat demand light is turning off the thermostat has satisfied 2 If DHW temp light is turning off the aquastat or call for domestic has been satisfi...

Page 34: ...fan is running air switch may be faulty 4 If fan is not running check 120V wiring to blower if ok remove low voltage harness from blower if blower fails to start replace blower if blower does start p...

Page 35: ...gas valve when it opens If boiler lights check for flame signal between FC1 And FC2 on Fenwal control If lower then 1 2 micro amps see Boiler will not stay lit below Check combustion properties If the...

Page 36: ...vent from the boiler during ignition if unit lights smoothly with intake vent disconnected reconnect and check for proper combustion if unit maintains smooth operation after ignition Calibrate for pr...

Page 37: ...ure the resistance of the thermister when disconnected 2 Using the appropriate chart find the resistance and move vertically for the water probe or horizontally for the air probe until the line is int...

Page 38: ...GT INSTALLATION AND OPERATION INSTRUCTIONS Page 38 Figure 48 Replacement Parts Exploded View SIOM 36...

Page 39: ...8 1 1 24 2 Clamp GT 82100 1 1 25 Sentry 2100 Control GT 82013 1 1 26 Complete Control Panel Assy GT 82754 1 1 27 PCB Optocoupler GT 82754 1 1 1 28 Outdoor Air Sensor 10K GT 81027 1 1 1 29 Transformer...

Page 40: ...WESTCAST INC 260 NORTH ELM STREET WESTFIELD MA 01085 TEL 413 562 9631 FAX 413 562 3799...

Reviews: