IDX-OM-W089
Air Dryer
14 Specification for Option T
IDFA6E-20 14 – 2 14-3 Remote operation
Terminal block
Power cable inlet
Power cable inlet
Power cable inlet
Power cable inlet
(
(
(
(Φ
Φ
Φ
Φ17)
17)
17)
17)
Rubber grommet(Base hole Φ22)
Signal cable inlet
Signal cable inlet
Signal cable inlet
Signal cable inlet
(
(
(
(Φ
Φ
Φ
Φ21)
21)
21)
21)
Rubber grommet(Panel hole Φ28)
14-3 Remote operation
・
For the remote operation, turn on and off the power supply side under the condition of the
Switch with Lamp ON.
・
Ensure at least 3 minutes is left after the unit is stopped before restarting it, even for the
remote operation. If the product is restarted within less than 3 minutes, protective
equipment (overload relay) may activate and prevent the product from restarting.
Additionally, the frequency to start and stop the operation must be restricted to 5 times
per hour (to prevent breakage of the motor).
14-4 How to connect the power supply and signal cable
Connect the power cable and signal cable in the following procedures.
1) Take off the rear panel.
2) Insert the power cable prepared by the customer into the power cable inlet (with rubber
grommet) and bring the power cable near the terminal block through the base hole.
Connect the power cable to the terminal.
3) Insert the signal cable prepared by the customer into the signal cable inlet (with rubber
grommet) and bring the signal cable near the terminal block.
4) Put back the rear panel.
3
お客様接続側
L N
1 2
PE
Rear panel
Customer connection side
Terminal connecting screw: M3
Crimping terminal width: 6.5mm and below
Applicable electrical wire:1.25mm
2
or more
L,N:Power
PE:Ground
1,2:Operation
2,3:Failure