HRX-OM-W002-A
Chapter 5 Display and Setting of Various Functions
HRR Series
5.5 Advanced setting mode
5-43
Table 5.5-1 List of alarms for which isolated pump operation is available
* 1 Select from OFF/ WRN/ FLT
2
Select from WRN/ FLT.
* 3 Can be set only for air-cooled type.
* 4 Option DM (Electric conductivity control type, de-ionized water piping type) only. Alarm is
automatically released when the electric conductivity returns within the range.
Temperature for pump to continue operation when alarm is generated.
28.
Press the [▼] key. Displays screen for setting the upper limit of temperature for the
pump to continue operation when an alarm is generated.
●Setting range: 10.0 to 45.0
℃
(initial value: 40.0
℃
)
Refer to P.5-42
“Isolated operation of the pump” for settings.
℃
PUMP
⇒
TEMP
(
Alternately displayed
)
Upper limit of the circulating fluid temperature for isolated
operation of the pump
Upper line
(White)
Lower line
(Green)
AL01
Low level in tank
FLT
AL01
LOW
⇒
LEVEL
⇒
FLT
-
AL02
Low level in tank
WRN
AL02
LOW
⇒
LEVE
⇒
WRN
-
AL04
Water leakage
WRN
1
AL04
WATER
⇒
LEAK
○
AL09
Circulating fluid
discharge pressure rise
FLT
2
AL09
HIGH
⇒
PRESS
-
AL10
Flow rate decreased
WRN
1
AL10
LOW
⇒
FLOW
⇒
WRN
○
AL11
Ambient temperature is
out of the range *3
OFF
1
AL11
AMB
⇒
TEMP
⇒
OUT
○
AL12
Electric conductivity
increase *4
WRN
AL12
DI
⇒
ERROR
-
AL13
NOT TEMP READY
OFF
1
AL13
TEMP
⇒
READY
⇒
ERROR
○
AL14
Circulating fluid
temperature increase
OFF
1
AL14
TEMP
⇒
OUT.HI
○
AL15
Circulating fluid
temperature decrease
OFF
1
AL15
TEMP
⇒
OUT.LO
○
AL17
Low flow rate
FLT
AL17
LOW
⇒
FLOW
⇒
FLT
-
AL18
High circulating fluid
discharge temp.
FLT
AL18
TEMP
⇒
FLT
-
AL19
High circulating fluid
return temp.
FLT
AL19
RET
⇒
TEMP
⇒
FLT
○
AL21
High circulating fluid
discharge pressure
FLT
AL21
HIGH
⇒
PRESS
⇒
FLT
-
AL24
Memory error
FLT
AL24
MEM
⇒
ERROR
○
AL25
Contact input 1
FLT
1
AL25
INP1
⇒
ERROR
○
AL26
signal detection
FLT
1
AL26
INP2
⇒
ERROR
○
AL27
Contact input 2
FLT
AL27
FORCE
⇒
STOP
-
AL28
signal detection
OFF
1
AL28
MANT
⇒
ALARM
○
AL29
Forced stop
WRN
1
AL29
COMM
⇒
ERROR
○
AL30
Notice for maintenance
FLT
AL30
REF
⇒
ERROR
⇒
0000
○
AL31
Communication error
FLT
AL31
SENS
⇒
ERROR
⇒
0000
-
AL32 Compressor circuit error
FLT
AL32
CTRL
⇒
ERROR
⇒
0000
-
Alarm
no.
Alarm name
Initial
value
Display
Alarms for which isolated
pump operation is
available