HRX-OM-W002-A
Chapter 9 Documents
HRR Series
9.1
Specifications
9-1
Chapter 9 Documents
9.1 Specifications
9.1.1
HRR012/018/024/030-A
-20-(DMTUY)
Table
9-1
Specifications [HRR012/018/024/030-A
-20-(DMTU)]
Model
HRR012-A
-20-(DMTUY)
HRR018-A
-20-(DMTUY)
HRR024-A
-20-(DMTUY)
HRR030-A
-20-(DMTUY)
Cooling method
Air-Cooled refrigerated type
Refrigerant
R410A(HFC)
Quantity of refrigerant
Kg
0.38
0.38
0.47
0.47
Control method
PID
control
Ambient temperature andhumidity and altitude
1
Temperature:
5 to 40
℃、
Humidity
:30 to 70%
、
Altitude
:
Less than 3000m
Circulating
fluid
system
Circulating fluid
2
Tap water, Ethylene glycol aqueous solution 15%
Operating temperature
range
1
℃
10 to 35
Cooling capacity
(50/60Hz)
3
W
1000/1200
1600/1800
2000/2400
2500/3000
Heating capacity
(50/60Hz)
4
W
450/500
550/700
Temperature stability
5
℃
±0.1
Pump capacity
(50/60Hz)
6
L/min
0.13
(
at 7L/min
)
/0.18(at 7L/min)
For option
–T : 0.42
(
at 10L/min
)
/0.4(at 14L/min
)
For option
–MT : 0.32
(
at 10L/min
)
/0.32(at 14L/min
)
Rated flow rate
(50/60Hz)
7
L/min
7 / 7
For option
–T ,-MT
:
10/14
Flowdisplay range
L/min
3 to 16
Electric conductivity
display range
µS/cm
2 to 48(For option -DM)
Electric conductivity
setting range
µS/cm
5 to 45(For option -DM)
Particle filter nominal
filtration rating
µm
5
Bypass valve
Installed
Tank capacity
L
Approx.
4
Fluid outlet,fluid return port port size
Rc1/2
Drain port size
Rc1/4,With cap
Leakage protection
Drain pan (With water leakage detector )
Fluid contact part material
Stainless steel,Copper brazing (Heat exchanger)
12
,Brass
17
,SiC,
Aluminum oxide ceramic,Carbon,PP,PE,POM,PA,FKM,EPDM,PVC,
PPS,AS,fluoropolymer
13
,Ion exchange resin
13
Electrical
system
Power supply
1-phase AC200 to 230V 50/60Hz
Allowable voltage fluctuation±10%
15
Circuit protector
A
10
(For option -T,-MT
:
15)
Applicable earth leakage breaker
8
Rated current
:
10A
(For option -T,-MT
:
15A)
Sensitivity current
:
30mA
Cable Qty x size(Incuding ground)
16
3 cores ×14AWG(3 cores×2.0m
㎡
)
Rated operating current
(50/60Hz)
3
A
3.6/4.0
3.6/4.3
5.2/5.8
5.5/6.2
For option -T,-MT
4.7/6.2
4.7/6.5
6.3/8.0
6.5/8.3
Rated power consumption
(50/60Hz)
18
Kw
(kVA)
0.6/0.8/
(0.7/0.8)
0.7/0.9
(0.7/0.9)
0.9/1.2
(1.1/1.2)
1.0/1.2
(1.1/1.3)
For option -T,-MT
0.9/1.2
(0.9/1.2)
0.9/1.3
(1.0/1.3)
1.2/1.6
(1.3/1.6)
1.3/1.6
(1.3/1.7)
Communication function
Contact input / output, Serial RS-485 / RS-232C
Noise level (50/60Hz)
9
dB
59/60
59/60
61/64
61/64
Dimensions
10
mm
W483xD550xH310
W483xD550xH399
Accessory
19
power supply connector,Maintenance handle for particle filter,
Operation manual,Particle filter element
Weight
11
kg
40
46
1: Use the product in conditions where freezing will not occur. Consult with SMC if using in a season or region where
the ambient temperature will fall below zero.
2: If tap water is used, use water which satisfies the standard of The Japan Refrigeration And Air Conditioning
Industry Association (JRA GL-02-1994/Cooling water system
–circulation type - make-up water).
3: (1)Ambient temp: 25
℃
, (2)Circulating fluid temp.: 20
℃
, (3)Circulating fluid rated flow, (4)Criculating
fluid : Tap water,(5)Power supply : AC200V, (6)Piping length : Shortest The cooling capacity will be reduced by
300W when option T and MT [High pressure pump] are selected.