HRX-OM-W002-A
Chapter 5 Display and Setting of Various Functions
HRR Series
5.5 Advanced setting mode
5-23
■
Example of MODE 3
When the offset temperature is 1
o
C, the thermo-chiller controls the temperature at 31
o
C
(circulating fluid set tempe offset temperature) Even if the discharge temperature is
31
o
C, the circulating fluid temperature is 30
o
C at the customer’s device because of 1
o
C of
heat radiation during sending of the fluid. The circulating fluid display temperature and the
communication data is 30
o
C (circulating fluid discharge temp. - offset temp.), and matches the
circulating fluid temperature at the customer's device.
To switch the offset mode, press the [ENT] key. "OFF" flashes,
p
ress the [▲], [▼] key, select "OFF", "MD1", "MD2", "MD3" and confirm with [ENT] key.
Offset temperature
7.
Press the [
▼] key. Displays offset temperature setting screen.
To change the offset temperature, press the [ENT] key. "0.0" flashes,press
the [▲], [▼] key to
change the offset temperature.
When the [ENT] key is pressed, the flashing ends and the offset temperature is fixed.
Circulating fluid display
temperature
29
℃
Circulating fluid set
temperature
30
℃
Offset temperature
-1
℃
This produuct
Your system
Serial communication
Discharge
temperature 30
℃
29℃
Circulating fluid
temperature 29
℃
Heat
radiation
1
℃
Circulating fluid display
temperature
30
℃
Circulating fluid set
temperature
30
℃
Offset temperature
1
℃
This produuct
Your system
Serial communication
Discharge
temperature 31
℃
30℃
Circulating fluid
temperature 30
℃
Heat
radiation
1
℃
℃
RUN
Offset temperature
:
Set within the range of -20.0 to 20.0°C
OFSET
⇒
TEMP
(
Alternately displayed
)