Chapter 5 Display and Setting of Various Functions
HRR Series
5.3 List of parameters
5-9
5.3.6
Alarm Setting Menu
Table
5.3-6
Alarm setting menu Parameter list
1
Can only be set with option DM(Electric conductivity control function,DI water (pure water) piping).
2
Can only be set with air-cooled type.
Initial value
Select/setting range
TOP
screen
-
AL.ST
-
MENU
-
No.1
screen
Changing of 「AL09:circulating fluid
discharge pressure rise」
FLT
WRN/FLT
HI.PRS⇒ALARM
-
No.2
screen
Setting for 「AL09:circulating fluid
discharge temperature rise」
0.50
0.05 to 0.50
HI.PRS
MPa
No.3
screen
Detection time for 「AL09:circulating
fluid discharge temperature rise」
5
0 to 60
HI.PRS⇒TIME
SEC
No.4
screen
Changing of 「AL10:lower flow rate」
WRN
OFF/WRN/FLT
LO.FL⇒ALARM
-
No.5
screen
Setting for 「AL10:lower flow rate」
4.0
3.0 to 15.0
LO.FL
LPM
No.6
screen
Detection time for 「AL10:lower flow rate」
5
0 to 600
LO.FL⇒TIME
SEC
No.7
screen
Setting for 「AL12:electric conductivity
control pressure rise alarm」(
μ
S/cm)*1
45.0
5.0 to 45.0
DI.HI
-
No.8
screen
Changing of 「AL.13:NOT TEMP READY alarm」
OFF
OFF/WRN/FLT
TEMP⇒READY⇒ALARM
-
No.9
screen
Output setting of 「AL.13:NOT TEMP READYalarm」
ON
OFF/ON
TEMP⇒READY⇒OUT.P
-
No.10
screen
Changing of 「AL14:circulating fluid
temperature rise」
OFF
OFF/WRN/FLT
TEMP⇒OUT.HI⇒ALARM
-
No.11
screen
output setting of 「AL14:circulating fluid
temperature rise」
ON
OFF/ON
TEMP⇒OUT.HI⇒OUT.P
-
No.12
screen
Changing of 「AL15:circulating fluid temperature drop」
OFF
OFF/WRN/FLT
TEMP⇒OUT.LO⇒ALARM
-
No.13
screen
Output setting of 「AL15:circulating fluid
temperature drop」
ON
OFF/ON
TEMP⇒OUT.LO⇒OUT.P
-
No.14
screen
Changing of 「AL11:Ambient temperature alarm」*2
OFF
OFF/WRN/FLT
AMB⇒TEMP⇒ALARM
-
No.15
screen
Upper limit of 「AL11:Ambient temperature alarm」*2
40.0
10.0 to 45.0
HI.TMP
℃
No.16
screen
Lower limit 「AL11:AL11:Ambient temperature alarm」*2
10.0
5.0 to 40.0
LO.TMP
℃
No.17
screen
Changing of [AL04:water leakage」
WRN
OFF/WRN/FLT
WATER⇒LEAK⇒ALARM
-
No.18
scree
Changing of「AL25: Contact input signal
1 detection」
FLT
OFF/WRN/FLT
INP1⇒ALARM
-
No.19
screen
「AL25:Contact input signal 1detection」
delay timer for reading
0
0 to 300
INP1⇒DELAY
SEC
No.20
screen
「AL25:Contact input signal 1 detection」
OFF detection timer
0
0 to 10
INP1⇒OVER
SEC
No.21
screen
Changing of 「AL26:Contact input signal 2 detection」
FLT
OFF/WRN/FLT
INP2⇒ALARM
-
No.22
screen
「AL26:Contact input signal 2 detection」
delay timer for reading
0
0 to 300
INP2⇒DELAY
SEC
No.23
screen
「AL26:Contact input signal 2 detection」
OFF detection timer
0
0 to 10
INP2⇒OVER
SEC
No.24
screen
Changing of「AL29:Communication error alarm」
WRN
OFF/WRN/FLT
COMM⇒ALARM
-
No.25
screen
Detection time for 「AL29:Communication error alarm」
30
1 to 600
COMM⇒TIME
SEC
No.26
screen
Only when the abnormality occurs time for isolated
operation of the pump
0
0 to 9999
PUMP⇒TIME
SEC
No.27
screen
Only when the abnormality occurs Pump
only possible operation temperature
40.0
10.0 to 45.0
PUMP⇒TEMP
℃
No.28
screen
Switching of notice for maintenance
OFF
OFF/WRN/FLT
MANT⇒ALARM
-
5.5.4
ScreenNo.
Item
Display unit
Unit
display
Reference
page
Upper stage(White)
Lower stage
(Green)