HRX-OM-W002-A
Chapter 5
Display and Setting of Various Functions
5.3 List of parameters
HRR Series
5-8
5.3.5
Standard setting menu
Table 5.3-5 Standard setting menu parameter list
1
Can only be set with option DM (Electric conductivity control function, DI water (pure water)
piping).
2
Can only be set with air-cooled type.
Initial value
Select/setting range
TOP
screen
-
SET
-
MENU
-
No.1
screen
Key-lock
OFF
OFF/ON
KEY⇒LOCK
-
No.2
screen
Basic setting mode
ON
OFF/ON
EASY⇒MODE
-
No.3
screen
Key click sound
ON
OFF/ON
KEY⇒CLICK
-
No.4
screen
Alarm buzzer
ON
OFF/ON
ALARM⇒BUZZ
-
No.5
screen
Offset mode
OFF
OFF/MD1/MD2/MD3
OFSET⇒MODE
-
No.6
screen
Offset temperature
0.0
-20.0 to 20.0
OFSET⇒TEMP
℃
No.7
screen
Electric conductivity control *1
Ctrl
Ctrl/OPEN/CLSE
DI⇒Ctrl
-
No.8
screen
Electric conductivity
setting value(
μ
S/cm)*1
25.0
5.0 to 45.0
DI.SP
-
No.9
screen
Electric conductivity
Hysteresis setting value(
μ
S/cm)*1
5.0
2.0 to 10.0
DI.HIS
-
No.10
screen
Unused
OFF
-
EXT⇒Ctrl
-
No.11
screen
Unused
0.0
-
EXT⇒OFSET
℃
No.12
screen
Unused
35.0
-
EXT⇒HI.TMP⇒LIMIT
℃
No.13
screen
Unused
10.0
-
EXT⇒LO.TMP⇒LIMIT
℃
No.14
screen
Unused
10
-
EXT⇒TIME
SEC
No.15
screen
TEMP READY bandwidth upper limit
1.0
0.1 to 9.9
READY⇒H.BAND
℃
No.16
screen
TEMP READY bandwidth lower limit
-1.0
-0.1 to -9.9
READY⇒L.BAND
℃
No.17
screen
TEMP READY stability time
180
10 to 9999
READY⇒TIME
SEC
No.18
scree
TEMP READY alarm of monitoring start time
600
0 to 9999
READY⇒STARM
SEC
No.19
screen
Time TEMP READY remove
5
0 to 600
TEMP⇒OVER
SEC
No.20
screen
Upper limit of circulating fluid
temperature monitor
40.0
10.0 to 45.0
TEMP⇒OUT⇒HI.TMP
℃
No.21
screen
Lower limit of circulating fluid temperature monitor
5.0
5.0 to 40.0
TEMP⇒OUT⇒LO.TMP
℃
No.22
screen
Monitor circulating fluid temperature
rise / drop alarm
rn.st
rn.st/PW.on
TEMP⇒OUT⇒ALARM
℃
No.23
screen
Start time of circulating fluid temperature monitor
600
0 to 9999
TEMP⇒OUT⇒StART
SEC
No.24
screen
circulating fluid temperature monitor is outside
of the time range
5
0 to 600
TEMP⇒OUT⇒OVER
SEC
No.25
screen
Dust filter replacement time*2
5000
1 to 9999
FLTR⇒TIME
H
No.26
screen
DI filter replacement time*1
5000
1 to 9999
DI⇒TIME
H
5.5.3
ScreenNo.
Item
Display unit
Unit
display
Reference
page
Upper stage(White)
Lower stage
(Green)