HRX-OM-W002-A
Chapter 3 Transport and Setting Up
3.3 Installation
HRR Series
3-14
3.3.5
Wiring of run/stop signal input and remote signal input
Run/Stop signal input and remote signal input enable the product to run/stop
remotely by applying a contact signal input. This chapter illustrates examples
of wiring.
To enable the run/stop signal input or remote signal input, after wiring, set the
item "Contact input signal 1 function selection" in "Communication setting
menu" from
"OFF (initial setting value)" → to "RN .ST ".
【
Tips
】
This product has two input signals. These can be customized depending on
the customer’s application.
1.
Prepare a suitable connector cable.
2.
Wire the contact input / output signal connector as shown below and connect it to this
product.(This wiring is an example, please refer to the instruction manual
"Communication function" for details.)
Fig 3-6
Wiring of run/stop signal input (Example)
8
1
15
9
Dsub 15 pin female (socket) type
←
Run/stop signal
Contact input/output signal connector
〃
1
4
9
Pin No.
〃
〃
11