HRX-OM-X084
Chapter 8
Control, Inspection, Exchange and Cleaning
8.3
Stop for a Long Time
HRR Series
8-10
5.
Remove the filter case.
Tilt the filter case to the front.
Please note that circulating fluid may flow out from the case when removing filter case.
Discharge circulating fluid inside of filter case.
After discharging circulating fluid, mount the resin filter case by hand tighten.
Caution
Mounting of the case should be performed by hand-tighten. When
the case is tightened excessively by tools , the case might crack or
be damaged.
If the case is dropped, it may result in cracking or breakage.
6.
Use a cross slot screwdriver to install the filter panel.
(Recommended tightening torque
:
1.5N
・
m)
Filter case
Tilt to the front
Open
Close