Chapter 5 Display and Setting of Various Functions
HRR Series
5.5 Advanced setting mode
5-33
DI filter replacement time
The DI filter maintenance time can be set by the user as a reminder to replace the
filter. Notice for maintenance "MT.05: DI filter maintenance" will be generated after
the set time has elapsed.
For maintenance notification, refer to "5.4.4 Notice for maintenance Menu".
The factory default setting is 5000 hours.
The time can be set in the range of 1 to 9999 hours.
Temperature control speed
28.
Press the [▼] key. Displays temperature control speed setting screen.
Can be set from the serial "yR
"
Temperature control speed
Change the temperature control speed.
The initial value is "0"
The higher the value, the temperature control will be fast.
The smaller the value, the temperature control will be slow.
5.5.4 Alarm setting menu
For some alarms, you can change the behavior and alarm threshold of when
an alarm occurs.
Alarm setting menu TOP screen
1.
When the [MENU] key is pressed while the Basic setting menu TOP screen is
displayed, "Alarm setting Menu TOP screen" is displayed.
Changing of circulating fluid discharge pressure rise alarm behaviour
2.
Press the [▼] key. Displays screen for changing the chiller behaviour when the
circulating fluid discharge pressure rise alarm occurs.
RUN
RUN
RUN
Alarm setting menu TOP screen
H
I
PRS
⇒
ALARM
(
Alternately displayed
)
Operation at occurrence of circulating fluid
discharge pressure rise alarm
Temperature control speed
CTRL
⇒
SPEED
(
Alternately displayed
)