Chapter 5 Display and Setting of Various Functions
HRR Series
5.5 Advanced setting mode
5-25
Electric conductivity setting value
The set value of electric conductivity can be set within the range of "0.5 to 45.0
μS / cm".The initial value is "25.0 μS / cm".
When the [ENT] key is pressed
, the set value flashes. Press the [▲], [▼] key to
change the set value. When the [ENT] key is pressed, the flashing ends
and the set value is confirmed.
Electric conductivity hysteresis
10.
Press the [▼] key. Displays electric conductivity hysteresis setting screen.
* Displayed only when option DM [Electric conductivity control function , DI water (pure
water) piping] is selected.
Electric conductivity hysteresis
The electric conductivity control hysteresis can be set within a range of "0.1 to 10.0
μS / cm" . The initial value is "5.0 μS / cm".
For the control image of electric conductivity by hysteresis, refer to "6.1 Option DM
[Electric conductivity control function , DI water (pure water) piping].
To change the setting value, press the [ENT] key. Hysteresis set value flashes,
p
ress the [▲], [▼] key to change the set value.
When the [ENT] key is pressed, the flashing ends and the set value is confirmed.
11.
Press the [▼] key. Display as shown below. It is not used with this product.
12.
Press the [▼] key. Display as shown below. It is not used with this product
RUN
RUN
RUN
℃
Electric conductivity
control hysteresis set value Unit: μS / cm
EXT
⇒
CTRL
(
Alternately displayed
)
EXT
⇒
OFSET
(
Alternately displayed
)
Unused
Unused