HRX-OM-X084
Chapter 5 Display and Setting of Various Functions
HRR Series
5.5 Advanced setting mode
5-57
Reset the operation time of the DI filter
7.
Press the [▼] key. Displays screen for resetting the operation time of the DI filter.
Displayed for the option DM (Electric conductivity control type, de-ionized water piping
type) only.
When the operation time of the DI filter
is reset, the operation time becomes “0 hour”.
When MT.05: Notice of DI filter maintenance is generated, reset the notice for DI filter
maintenance.
Press “ENT” key when resetting the operation time of the DI filter. When the display is
flashing, press [
▲], [▼] key and select “YES”. Then, press “ENT” key.
DI solenoid valve forced open
8.
Press the [▼] key. Displays screen for setting DI solenoid valve.
Displayed for option DM (Electric conductivity control type, de-ionized water piping
type) only. The DI solenoid valve can open or close while the operation is stopped.
Press [ENT] key to set the DI solenoid valve when the operation is stopped. When the
display is flashing, press [▲], [▼] key and select “YES”. Then, press “ENT” key.
Set value
Contents
Initial value
NO
Not reset.
○
YES
Reset the operation time of the DI filter.
-
Set value
Contents
Initial value
OFF
DI solenoid valve: CLOSE
○
ON
DI solenoid valve: OPEN
-
D
I
T
⇒
RESET
(
Alternately displayed
)
Reset the DI filter operation time
Setting of DI solenoid valve
DI
⇒
VALVE
(
Alternately displayed
)