6.2 Option M
【
DI water (Pure water) piping
】
HRR Series
6-2
6.2 Option M
【
DI water (Pure water) piping
】
6.2.1 Option M
【
DI water (Pure water) piping
】
This option is for customers who use DI water (pure water) as circulating fluid.
Circulating fluid wetted materials
Stainless (include heat exchanger brazing),
Aluminum oxide ceramic, Carbon, PP, PE,PA,PPE,
POM,PET,PPS, FKM, EPDM, NBR,PVC
(No. copper used)
This M option does not have electric resistance/ electric conductivity
control function.If this function is necessary, option DM
【
Electric
conductivity control function, DI water(Pure water piping)
】
should be
choose.
6.3 Option T1
【
Inverter pump
】
6.3.1
Option T1
【
Inverter pump
】
With option T1 (Inverter pump), The pump output set value can be changed.
This pump has a sealless structure.
Applicable model
HRR010-A/W-10/20-T1
Pump
Rated flow*
1
(50/60Hz
common)
L/min
5
Maximum pump
head*
2
(50/60Hz common)
m
35
Output
W
400
Circuit protector
A
15
Recommended earth leakage
breaker capacity
A
15
Cooling capacity
W
Due to an increase in heat generation of the pump.
The cooling capacity reduces about 300W from the value in the catalog.
*1 Required minimum flow rate for cooling capacity or maintaining the temperature stability.
*2 The capacity at the thermo-chiller outlet when the circulating fluid temperature is 20
℃
.
Note) When the option, Inverter pump, is selected, the product weight is increased by 1 kg.
Note) No change in external dimensions of this product.