Chapter 5
Display and Setting of Various Functions
5.5 Advanced setting mode
HRR Series
5-52
Contact output signal 2 Operation
18.
Press the [▼] key. Displays screen for setting the operation of the Contact output
signal 2.
Select the Contact output signal 2 operation.
Set value
Contents
Initial value
A
N.O. type
○
B
N.C. type
―
Contact output signal 2 Select alarm
19.
Press the [▼] key. Displays screen for setting the selected alarm of the Contact output
signal 2.The alarm is valid when the “selected alarm status signal output” is active.
Select the alarm No. to be allocated to Contact output signal 2
●Setting range: AL.01 to AL.32 (Initial value: AL.01)
Contact output signal 2 Select maintenance
20.
Press the [▼] key. Displays screen for setting the selected maintenance of the Contact
output signal 2. The alarm is val
id when the “selected maintenance status signal output”
is selected.
Select the maintenance alarm No. to be allocated to Contact output signal 2.
●
Setting range: MT.01 to MT.05 (Initial value: MT.01)
Contact output signal 3 Select function
21.
Press the [▼] key. Displays screen for setting the function of the Contact output signal
3.
D
OUT
⇒
SEL
(
Alternately displayed
)
Contact output signal 2 operation
Contact output signal 2 Selected alarm No.
Contact output signal 2 Selected maintenance alarm No.
Contact output signal 3 function
D
OUT3
⇒
SEL
(
Alternately displayed
)
D
OUT2
⇒
ALARM
⇒
CODE
(
Alternately displayed
)
D
OUT2
⇒
MANT
⇒
CODE
(
Alternately displayed
)