-48-
No.EX##-OMV0017-D
4.4 Forced output
4.4.1 Forced output conditions
The I/O Configurator (NFC version) can directly command the Wireless Base / Remote.
Operating conditions for forced output.
[Forced output from the Wireless Base]
[Forced output from the Wireless Remote]
Forced output
conditions
Login to Administrator mode.
Not connected with the PLC by Ethernet.
Login to Administrator mode.
Not wirelessly connected with Wireless Base.
Applicable item
for forced output
Wireless Base / Remote
Wireless Remote
Forced output procedure (digital unit)
Forced output is performed in forced output mode. Data can be output in either bit or byte units.
[Forced output in bit units]
Click the [I/O monitor] tab, and switch to the [Output] tab. Check mark the "Enforce ON" box at the upper
right of the window. In the dialog box select [Yes] to confirm enabling forced output.