3.7 Software Control
"HOLD/CLR setting (unit): Software control" of "Base / Remote setting", the output operation for when the
Ethernet communication is disconnected, can be selected for valve output or output unit independently, in 1-
point units, using "CLEAR", "HOLD", or "SET". The values for the Hold / Clear for each valve output or
output unit are stored in the unit with outputs.
Set value
Description
HOLD
Maintain the value before Hold / Clear.
CLEAR
0 for Hold / Clear
SET
1 for Hold / Clear
* Editing is possible from the "Description" on the Information tab when "HOLD/CLR (unit)" is set to "Software Control".
In order to set "HOLD/CLR (unit)" to "Software Control", change the setting using "Base setting" or "Remote setting"
in the "Properties" tab.
* The output operation when wireless communication is disconnected is "HOLD" regardless of the setting of Software
Control.
Hold / Clear setting procedure
(1) Display the description of the output unit.
(For how to display the description, refer to "5.1.2 System configuration area".)
(2) The window for Unit HOLD/CLR/SET setting appears by clicking the [Edit] button.
From the left
Bit 0, 1, 2, 3, 4, 5, 6, 7
Displayed when
Software Control is
selected.