-27-
No.EX##-OMV0017-D
System setting items (example using manifold-type Wireless Base EX600-WEN# / EX600-WPN#)
Parameter
Set value
Initial value
I/O mapping
Manual / Auto
Manual (EX600-WEN#)
Auto (EX600-WPN#, fixed)
System input size
16, 128 to 1280 points (2 bytes to 160 bytes) in 128-
point (16-byte) units
1280 points/160 byte
System output size
16, 128 to 1280 points (2 bytes to 160 bytes) in 128-
point (16-byte) units
1280 points/160 byte
Diagnostic allocation
None / Simple / Advanced
Advanced
Max. Remote units
0 / 15 / 31 / 63 / 127 Remotes (EX600-WEN#)
0 / 15 / 31 units (EX600-WPN#)
15 Remotes
DA refresh time(sec)*
1
0.1 / 0.2 / 0.5 / 1 / 2 / 5 / 10 / 30 / 60 s
1 s
*1 The analog input update time is set for every Wireless Remote unit. Refer to "3.3 Remote setting".
●
Wireless communication setting
With a Wireless Base unit that supports CC-Link (EXW1-BMJA#), the frequency channel can be selected.
Frequency channel selecting function (F.C.S.)
Only protocol V.2.0 is supported. Specify protocol V.2.0 in [System setting].
* The number of selectable frequency channels varies depending on the country in use. For more details,
check the product number.
●
Countries other than USA, Canada, and South Korea: ch 5-79
●
USA, Canada, and South Korea: ch 15-79
* If no channel is selected, communication is established on ch 79 by default.
Make settings from [Remote registration] on the [Properties] tab.
(1) Set [Pairing] to [Normal mode].
Refer to "3.5 Pairing" for details on pairing.
(2) Click [FCS Setting].
(1)
(2)