LD291 - Operation and Maintenance Instruction Manual
4.4
Figure 4.3 shows branch CONF with the available options.
Figure 4.3 - Local Adjustment Configuration Tree
Configuration Branch (CONF)
Z:
Moves to the TRIM branch.
S:
Enters the CONFIGURATION branch, starting with function display (LCD_1).
Display 1 (LCD_1)
Z:
Moves to the function Display 2 (LCD_2).
S:
Starts selection of variable to be indicated as primary display.
After activating (
S
), you can move around the options available in the following
table by activating (
Z
). See table 4.3.
The desired variable is activated using (
S
). Escape leaves primary variable
unchanged.
Display 2 (LCD_2)
Z:
Moves to the RANGE function.
S:
Starts selection of variable to be indicated as secondary display.
The procedure for selection is the same as for LCD_1, previous.
CURRENT
CURRENT IN MILIAMPÈRES
CO
Analog Output Current in mA
PR
Pressre in pressure unit.
PV%
Process Variable in percentage.
PV
Process Variable in engineering units.
TE
Ambient temperature.
NONE - No variable on display (only LCD_2)
ESC
Escape.
Table 4.3 - Display Indication
Summary of Contents for LD291
Page 1: ...INTELLIGENT PRESSURE TRANSMITTER LD291 Version 6 MAR 12 L D 2 9 1 M E ...
Page 8: ...LD291 Operation and Maintenance Instruction Manual VIII ...
Page 11: ...Installation 1 3 Figure 1 1 b Dimensional Drawing and Mounting Position for LD291 Sanitary ...
Page 13: ...Installation 1 5 Figure 1 1 d Dimensional Drawing and Mounting Position for LD291 Level ...
Page 36: ...LD291 Operation and Maintenance Instruction manual 3 10 ...
Page 58: ...LD291 Operation and Maintenance Instruction Manual 5 12 ...
Page 70: ...LD291 Operation Maintenance Instruction Manual 6 12 ...
Page 74: ...LD291 Certifications Information A 4 NEMKO and DMT CEPEL ...
Page 76: ...LD291 Certifications Information A 6 CEPEL ...
Page 78: ...LD291 Certifications Information A 8 FM ...
Page 79: ...Appendix A A 9 NEMKO ...
Page 80: ...LD291 Certifications Information A 10 ...