Configuration
3.9
EXAMPLE:
1 2 3 4 5 6 7 8 9 10 11 12 13
L D 2 9 1 M 2 1I 1 1 0 1 H1
LD291 Intelligent Pressure Transmitter (D)
; Range: 1.25 to 50 kPa
(2)
; Diaphragm of 316L SS,
Silicone Oil Fill Fluid
(1)
, and Connection to the process with 316L SS
(1I)
; with Digital Indicator
(1)
;
Electrical Connection 1/2 - 14 NPT
(0)
; with Local Adjustment
(1)
; with Carbon Steel Bracket and
accessories
(1)
; housing in SS
(HI)
.
SERIAL NUMBER
- Three serial numbers are stored:
Circuit Number
- This number is unique to every main circuit board and cannot be changed.
Sensor Number
- The serial number of the sensor connected to the
LD291
and cannot be
changed. This number is read from the sensor every time a new sensor is inserted in the main
board.
Transmitter Number -
the number that is written at the identification plate each transmitter.
NOTE
The transmitter number must be changed whenever there is the main plate change to avoid
communication problems.
OP_COUNT
- Every time a change is made, there is an increment in the respective change
counter for each monitored variable, according to the following list. The counter is cyclic, from 0 to
255. The monitored items are:
LRV/URV:
when any type of calibration is done;
Function:
when any change in the transference function is done, e.g., linear, square root,
const, table;
Trim_4mA:
when the current trim is done at 4 mA;
Trim_20mA:
when the current trim is done at 20 mA;
Trim_Zero/Lower:
when pressure trim is done at Zero or Lower Pressure;
Trim Upper Pressure:
when the trim is done at Upper Pressure;
Characterization:
when any change is made in any point of the pressure characterization table
in trim mode;
Multidrop:
when any change is made in the communication mode, for example, multidrop or
single transmitter;
Pswd/C-Level:
when any change is made in the password or the level configuration.
BACKUP
When the main board is replaced, after assembling and powering it, the data saved in the sensor
memory are automatically copied to the main board memory.
RESTORE
This option allows copying or restoring the data saved in the sensor memory to the main board
memory.
Summary of Contents for LD291
Page 1: ...INTELLIGENT PRESSURE TRANSMITTER LD291 Version 6 MAR 12 L D 2 9 1 M E ...
Page 8: ...LD291 Operation and Maintenance Instruction Manual VIII ...
Page 11: ...Installation 1 3 Figure 1 1 b Dimensional Drawing and Mounting Position for LD291 Sanitary ...
Page 13: ...Installation 1 5 Figure 1 1 d Dimensional Drawing and Mounting Position for LD291 Level ...
Page 36: ...LD291 Operation and Maintenance Instruction manual 3 10 ...
Page 58: ...LD291 Operation and Maintenance Instruction Manual 5 12 ...
Page 70: ...LD291 Operation Maintenance Instruction Manual 6 12 ...
Page 74: ...LD291 Certifications Information A 4 NEMKO and DMT CEPEL ...
Page 76: ...LD291 Certifications Information A 6 CEPEL ...
Page 78: ...LD291 Certifications Information A 8 FM ...
Page 79: ...Appendix A A 9 NEMKO ...
Page 80: ...LD291 Certifications Information A 10 ...