LD291- Operation and Maintenance, Instruction manual
3.6
This calibration procedure is also recommended for zero suppression or elevation in those cases where
the instrument installation results in a residual measurement in relation to a certain reference. This is
the specific case of the wetted tap.
NOTE
In most applications with wetted taps, indication is usually expressed as a percentage. Should
readout in engineering units with zero suppression be required, it is recommended to use the User
Unit feature for such conversion.
Engineering Unit Selection
Transmitter
LD291
includes a selection of engineering units to be used in measurement indication.
For pressure measurements, the
LD291
includes an option list with the most common units. The
internal reference unit is inH
2
O @ 20
o
C; should the desired unit be other than this one, it will be
automatically converted using conversion factors included in Table 3.1.
As the
LD291
uses a 4 ½ digit display, the largest indication will be 19999. Therefore, when selecting a
unit, make sure that it will not require readouts greater than this limit. For User reference, Table 3.1
presents a list of recommended sensor ranges for each available unit.
CONVERSION FACTOR
NEW UNITS
RECOMMEND RANGE
1.00000
Inches H
2
O at 20
o
C
1, 2,3 & 4
0.0734241
Inches Hg at 0
o
C
all
0.0833333
Feet H
2
O at 20
o
C
all
25.4000
Millimeters H
2
O at 20
o
C
1 & 2
1.86497
Millimeters Hg at 0
o
C
1, 2, 3 & 4
0.0360625
Pound/square inch - psi
2, 3, 4, 5 & 6
0.00248642
Bar
3, 4, 5 & 6
2.48642
Millibar
1, 2, 3 & 4
2.53545
Gram/square centimeter
1, 2, 3 & 4
0.00253545
kilogram/square centimeter
3, 4, 5 & 6
248.642
Pascal
1
0.248642
KiloPascal
1, 2, 3 & 4
1.86497
Torr at 0
o
C
1, 2, 3 & 4
0.00245391
Atmosphere
3, 4, 5 & 6
0.000248642
MegaPascal
4, 5 & 6
0.998205
Inches of water at 4
o
C
1, 2, 3 & 4
25.3545
Millimeters of water at 4
o
C
1 & 2
Table 3.1 - Available Pressure Units
In applications where the
LD291
will be used to measure variables other than pressure or in the cases
where a relative adjustment has been selected, the new unit may be displayed by means of the User
Unit feature. This is the case of measurements such as level, volume, and flow rate or mass flow
obtained indirectly from pressure measurements.
The User Unit is calculated taking the working range limits as a reference, which is, defining a value
corresponding to 0% and another corresponding to 100% of the measurement:
0%
- Desired readout when the pressure is equal to the Lower Value (PV% = 0%, or transmitter
mode output equal to 4 mA).
100%
- Desired readout when the pressure is equal to the Upper Value (PV% = 100%, or
transmitter mode output equal to 20 mA).
The user unit may be selected from a list of options included in the
LD291
. Table 3.2 makes it possible
to associate the new measurement to the new unit so that all supervisory systems fitted with HART
protocol can access the special unit included in this table. The user will be responsible for the
consistency of such information. The
LD291
cannot verify if the values corresponding to 0% and 100%
included by the user are compatible with the selected unit.
Summary of Contents for LD291
Page 1: ...INTELLIGENT PRESSURE TRANSMITTER LD291 Version 6 MAR 12 L D 2 9 1 M E ...
Page 8: ...LD291 Operation and Maintenance Instruction Manual VIII ...
Page 11: ...Installation 1 3 Figure 1 1 b Dimensional Drawing and Mounting Position for LD291 Sanitary ...
Page 13: ...Installation 1 5 Figure 1 1 d Dimensional Drawing and Mounting Position for LD291 Level ...
Page 36: ...LD291 Operation and Maintenance Instruction manual 3 10 ...
Page 58: ...LD291 Operation and Maintenance Instruction Manual 5 12 ...
Page 70: ...LD291 Operation Maintenance Instruction Manual 6 12 ...
Page 74: ...LD291 Certifications Information A 4 NEMKO and DMT CEPEL ...
Page 76: ...LD291 Certifications Information A 6 CEPEL ...
Page 78: ...LD291 Certifications Information A 8 FM ...
Page 79: ...Appendix A A 9 NEMKO ...
Page 80: ...LD291 Certifications Information A 10 ...