LD291 - Operation and Maintenance Instruction Manual
1.8
GAS
STEAM
LIQUID
Figure 1.3 – Position of the Transmitter and Taps
NOTE
The transmitters are calibrated in the vertical position and a different mounting position displaces
the zero point. Consequently, the indicator will indicate a different value from the applied pressure.
In these conditions, it is recommended to do the zero pressure trim. The zero trim is to compensate
the final assembly position and its performance, when the transmitter is in its final position. When
the zero trim is executed, make sure the equalization valve is open and the wet leg levels are
correct.
For the absolute pressure transmitter, the assembly effects correction should be done using the
Lower trim, due to the fact that the absolute zero is the reference for these transmitters, so there is
no need for a zero value for the Lower trim.
Electronic Housing
Humidity is fatal to electronic circuits. In areas subjected to high relative humidity, the O-rings for the
electronic housing covers must be correctly placed and the covers must be completely closed by
tighten them by hand until you feel the O-rings being compressed. Do not use tools to close the covers.
Removal of the electronics cover in the field should be reduced to the minimum necessary, since each
time it is removed; the circuits are exposed to the humidity.
The electronic circuit is protected by a humidity proof coating, but frequent exposures to humidity may
affect the protection provided. It is also important to keep the covers tightened in place. Every time they
are removed, the threads are exposed to corrosion, since painting cannot protect these parts. Code-
approved sealing methods should be employed on conduit entering the transmitter.
WARNING
The unused cable entries should be plugged and sealed accordingly to avoid humidity entering,
which can cause the loss of the product’s warranty.
DIAPHRAGM
SENSOR IN THE VERTICAL
SENSOR IN THE HORIZONTAL
HEAD OF THE FLUID
DIAPHRAGM
Summary of Contents for LD291
Page 1: ...INTELLIGENT PRESSURE TRANSMITTER LD291 Version 6 MAR 12 L D 2 9 1 M E ...
Page 8: ...LD291 Operation and Maintenance Instruction Manual VIII ...
Page 11: ...Installation 1 3 Figure 1 1 b Dimensional Drawing and Mounting Position for LD291 Sanitary ...
Page 13: ...Installation 1 5 Figure 1 1 d Dimensional Drawing and Mounting Position for LD291 Level ...
Page 36: ...LD291 Operation and Maintenance Instruction manual 3 10 ...
Page 58: ...LD291 Operation and Maintenance Instruction Manual 5 12 ...
Page 70: ...LD291 Operation Maintenance Instruction Manual 6 12 ...
Page 74: ...LD291 Certifications Information A 4 NEMKO and DMT CEPEL ...
Page 76: ...LD291 Certifications Information A 6 CEPEL ...
Page 78: ...LD291 Certifications Information A 8 FM ...
Page 79: ...Appendix A A 9 NEMKO ...
Page 80: ...LD291 Certifications Information A 10 ...