4 Product Overview
SMA Solar Technology AG
Operating manual
SBSxx-10-BE-en-11
23
Do not connect any loads that require an uninterrupted energy supply
The secure power supply operation and the battery-backup operation may not be used for
loads that require a uninterrupted energy supply. The energy that is available during the
secure power supply operation or battery-backup operation depends on the battery capacity
available and the state of charge of the battery (SOC).
• Do not connect loads if they are dependent on an uninterrupted energy supply for
reliable operation.
Black start function
The inverter has a black start function and an auxiliary battery that provides energy for the black
start. In battery-backup systems, you have the possibility to install a standard switch for black
starting the inverter and battery. The black-start switch is used to start the battery-backup operation
manually in the event of grid failure if the battery and inverter are in sleep mode and, therefore, are
unable to provide energy. When the black-start switch is switched on manually, the energy from the
auxiliary battery is made available in order to automatically switch the battery and therefore also
the inverter from sleep mode to operation in order that the inverter can make energy available from
the battery. You can stop the battery-backup operation by switching it off manually. To enable the
black-start function, at least one battery must be connected to input A.
Multi-battery device
The product is equipped with the multi-battery function as standard from firmware version
1.50.10.R. The multi-battery function enables to charge and discharge several batteries of the same
or different type. If the system is extended by one or several batteries or one battery is replaced,
the battery configuration must be reset and carried out again. The configuration is carried out via
the installation assistant on the user interface of the battery inverter. An overview of batteries
approved by SMA Solar Technology AG and their possible combinations is available at
www.SMA-Solar.com.
All-pole sensitive residual-current monitoring unit
The all-pole sensitive residual-current monitoring unit detects alternating and direct differential
currents. In single-phase and three-phase inverters, the integrated differential current sensor detects
the current difference between the neutral conductor and the line conductor(s). If the current
difference increases suddenly, the inverter disconnects from the utility grid.
SMA Smart Connected
SMA Smart Connected is the free monitoring of the inverter via the SMA Sunny Portal. Thanks to
SMA Smart Connected, the PV system operator and qualified person will be informed automatically
and proactively about inverter events that occur.
SMA Smart Connected is activated during registration in Sunny Portal. In order to use SMA Smart
Connected, it is necessary that the inverter is permanently connected to Sunny Portal and the data
of the PV system operator and qualified person is stored in Sunny Portal and up-to-date.