Control Panel Installation
151430
4-3
4.3
Battery Connection
The control panel battery charge capacity is 17 to 55 AH. Use 12V batteries of the same AH
rating. Determine the correct AH rating as per your standby load calculation (see Section 3.6).
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase
the AH rating. It is recommended that you replace batteries every five years.
Figure 4-3 Battery Connection
To Control Panel
Red
Black
Battery Jumper
(P/N 140694)
Shipped With Panel
UL Recognized 12V Battery
UL Recognized 12V Battery