Reporting
151430
11-1
Section 11
Reporting
This section lists receivers that are compatible with this control panel, and the reporting codes
sent by the control panel for SIA and Contact ID formats.
11.1 Receivers Compatible with the Control Panel
Table 11-1 shows receivers compatible with the control panel.
11.2 Reporting Formats Table
Table 11-1: Receivers Compatible with the Control Panel
Manufacturer
Model
Format
Silent Knight
Model 9800
SIA and Contact ID
Model 9000 (SIA formats)
SIA
Ademco
Model 685 (Contact ID )
Contact ID
Sur-Gard
SG-MLR2-DG (V. 1.64 or higher)
SIA and Contact ID
Osborne Hoffman
Quickalert
SIA and Contact ID
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier (same as IFP-1000 Rev 9)
SIA IFP-2000
Event Description
Module ID #
(If Any)
SIA Event
Codes
Parameter
Fixed Length Format
NN - panel ID
XX - SBUS ID
ZZZ - zone #
PPPP - Point #
AAAAAA-account #
Qualifier
Event
Code
Group #
Contact #
System Events
Note:
System Events are reported when either
“
Report by Point
”
or Report by Zone is selected
AC power low trouble
AT
0
ATNN000000
1
301
00
000
AC power low trouble restore
AR
0
ARNN000000
3
301
00
000
Auto dialer test communications trouble line 1
YC
1
YCNN000001
1
350
00
001
Auto dialer test communications trouble line 1 restore
YK
2
YKNN000001
3
350
00
002
Auto dialer test communications trouble line 2
YC
1
YCNN000002
1
350
00
001
Auto dialer test communications trouble line 2 restore
YK
2
YKNN000002
3
350
00
002
Automatic test normal
RP
0
RPNN000000
1
602
00
000
Automatic test off normal
RY
0
RYNN000000
1
608
00
000
Battery voltage trouble
YT
Exp. ID
YTNNXX0000
1
302
Exp. ID
000
Battery voltage trouble restore
YR
Exp. ID
YRNNXX0000
3
302
Exp. ID
000
Date changed event
JD
0
JDNN000000
1
625
00
000
Fire drill has begun
FI
0
FINN000000
1
604
00
000
Fire drill has ended
FK
0
FKNN000000
3
604
00
000
Ground fault condition trouble
YP
Exp. ID
YPNNXX0000
1
310
Exp. ID
000
Ground fault condition trouble restore
YQ
Exp. ID
YQNNXX0000
3
310
Exp. ID
000
Initial power up
RR
0
RRNN000000
1
305
00
000
Local programming aborted or ended with errors
LU
0
LUNN000000
1
628
00
000
Summary of Contents for IFP-2000
Page 2: ......
Page 12: ...IFP 2000 Installation Manual viii...
Page 22: ...IFP 2000 Installation Manual 1 10 151430...
Page 26: ...IFP 2000 Installation Manual 2 4 151430...
Page 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example...
Page 100: ...IFP 2000 Installation Manual 5 14 151430...
Page 194: ...IFP 2000 Installation Manual 10 20 151430...
Page 210: ...IFP 2000 Installation Manual 12 8 151430...
Page 230: ...IFP 2000 Installation Manual A 14...
Page 232: ...IFP 2000 Installation Manual B 2 151430...
Page 236: ......
Page 237: ......