10.4.7 Conduct a Walk Test
1. From the Main Menu, press
for System Tests.
2. Select
for Walk Test-No Rpt. The LCD will display “WALK TEST STOPPED” on
Line 1 and “ENTER = start test” on Line 2. Enter the time period you wish the NAC cir-
cuit to be active for each alarm (06 to 180 second), if you select this option, central station
reporting will be disabled while the test is in progress.
Or
Select
for Walk Test-with Rpt. The LCD will display “WALK TEST STOPPED” on
Line 1 and “ENTER = start test” on Line 2. Enter the time period you wish the NAC cir-
cuit to be active for each alarm (06 to 180 seconds) If you select this option, central station
reporting will occur as normal during the walk test.
The panel generates a TEST report to the central station when the walk test begins. During
a walk test, the panel’s normal fire alarm function is completely disabled, placing the
panel in a local trouble condition. All zones respond as 1-Count zones (respond when a
single detector is in alarm) during a walk test. Each alarm initiated during the walk test
will be reported and stored in the event history buffer.
3. Press
to end the walk test. The system will reset. The panel will send a "TEST
RESTORE" report to the central station.
If you do not end the walk test manually within four hours, it will end automatically.
If an alarm or pre-alarm condition is occurring in the system, you will not be able to enter the
walk test.
Note: the panel does not do a full 30 second reset on resettable power outputs. As soon as the device is back to
normal, the panel is ready to go to the next device.
10.4.8 Conduct a Dialer Test
1. From the Main Menu, press
for System Tests.
2. Select
for Dialer Test. The screen will display “Manual dialer test started”. When the
test is completed, you will be returned to the <Test Menu>.
Important
If any alarm verification zones are being used, the user will be asked if they
wish to disable alarm verification during walk test. This occurs for either walk
test option.
1
3
4
1
5
Summary of Contents for IFP-2000
Page 2: ......
Page 12: ...IFP 2000 Installation Manual viii...
Page 22: ...IFP 2000 Installation Manual 1 10 151430...
Page 26: ...IFP 2000 Installation Manual 2 4 151430...
Page 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example...
Page 100: ...IFP 2000 Installation Manual 5 14 151430...
Page 194: ...IFP 2000 Installation Manual 10 20 151430...
Page 210: ...IFP 2000 Installation Manual 12 8 151430...
Page 230: ...IFP 2000 Installation Manual A 14...
Page 232: ...IFP 2000 Installation Manual B 2 151430...
Page 236: ......
Page 237: ......