IFP-2000 Installation Manual
4-36
151430
4.13.3 Installing 2-Wire Smoke Detectors
Any compatible U.L. listed two-wire smoke detector can be used with the control panel (see
for list of compatible smoke detectors). Figure 4-36 and Figure 4-37 illustrate how to connect
a UL listed 2-wire detector to the control panel.
4.13.3.1 Installing 2-Wire Class B Smoke Detectors
To install a Class B two-wire smoke detector, wire as shown in Figure 4-36.
Figure 4-36 Two-Wire Class B Smoke Detector
Note:
Flexput circuit 5
used as an example.
Any Flexput circuit
could be used.
UL Listed
EOL Model
7628
4.7 k
Ω
Maximum Impedance per
Circuit is 50
Ω
Supervised
Power Limited