IFP-2000 Installation Manual
6-4
151430
running the SKSS-2 (see also Section 10.4.15). In order for this communication to function
properly both the computer (running the software) and the control panel must have matching
computer account numbers and computer access codes.
Before you program in this location you should know how your control panel will
communicate with the downloading computer, either through direct connect USB or via the
phone lines (Internal Modem).
If the panel initiates the call to a downloading computer, a phone number must be
programmed in the computer accounts area. If the computer initiates the call, answering
machine bypass may need to be selected (see Section 9.6.2.6).
To program computer account information:
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select
for Network Programming.
3. Press to enter the Computer Account Menu.
4. Enter the computer code (up to 6-digits), then press
.
5. Enter the computer access code, then press
.
6. Enter the phone number the panel will dial to connect to a downloading computer (up to
40-digits), then press
.
6.2.5
Access Codes
Access codes provide the user access to the control panel functions. Each access code can be
customized for each user. This allows some users the ability to access programming and other
higher level panel functions, while other users may only need access to lower level functions
such as preforming fire drills, or acknowledging trouble conditions.
Profile 1 is the profile that dictates what functions the Fire Fighter Key has access to. (The
functions that are available once you open the cabinet door and before an access code is
entered). Because this is the profile for a key the user name and the access code can not be
edited for this profile.
Profile 2 is the profile for the installer and is referred to as the “Installer Code”. This profiles
user name and panel functions can not be edited.
Table 6-1 lists the panel functions that can be selected for each user profile.
6
4
Summary of Contents for IFP-2000
Page 2: ......
Page 12: ...IFP 2000 Installation Manual viii...
Page 22: ...IFP 2000 Installation Manual 1 10 151430...
Page 26: ...IFP 2000 Installation Manual 2 4 151430...
Page 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example...
Page 100: ...IFP 2000 Installation Manual 5 14 151430...
Page 194: ...IFP 2000 Installation Manual 10 20 151430...
Page 210: ...IFP 2000 Installation Manual 12 8 151430...
Page 230: ...IFP 2000 Installation Manual A 14...
Page 232: ...IFP 2000 Installation Manual B 2 151430...
Page 236: ......
Page 237: ......