05.2006
Technical Data
Siemens AG
6SE7087-2JD60
SIMOVERT MASTERDRIVES
Operating Instructions
13-7
Designation
Value
Order No.
6SE70... 16-1EA61 18-0EA61 21-0EA61 21-3EB61 21-8EB61 22-6EC61
Rated voltage
[V]
•
Input
•
Output
3 AC 380 (- 15 %) to 480 (+ 10 %)
3 AC 0 up to rated input voltage
Rated frequency
[Hz]
•
Input
•
Output:
V/f = constant
V = constant
50 / 60
±
6 %
0 to 600
8 to 300
Rated current
[A]
•
Input
•
Output
6.7
6.1
8.8
8.0
11.2
10.2
14.5
13.2
19.3
17.5
28.1
25.5
DC link voltage
[V]
510 (- 15 %) to 650 (+ 10 %)
Rated output
[kVA] 4.1 to 5.0
5.3 to 6.6
6.8 to 8.4 8.7 to 10.9
11.6 to 14.5 16.8 to 21.2
Auxiliary current supply
[V]
DC 24 (20 - 30)
•
Max. aux. curr. requirement[A]
Standard version at 20 V
1.5
•
Max. aux. curr. requirement[A]
Maximum version at 20 V
2.5
Pulse frequency
[kHz]
1.5 to 16 (see Fig. „Derating curves“)
Load class II to EN 60 146-1-1
Base load current
[A]
0.91 x rated output current
Base load duration
[s]
240
Overload current
[A]
1.36 x rated output current
Overload duration
[s]
60
Load class II to EN 60 146-1-1 (additional)
Base load current
[A]
0.91 x rated output current
Base load duration
[s]
270
Overload current
[A]
1.6 x rated output current
Overload duration
[s]
30
Losses, cooling, power factor
Power factor
•
Line cos
ϕ
1L
•
Converter cos
ϕ
C
≥
0.98
< 0.92 ind.
Efficiency
η
(rated operation)
≥
0.97
≥
0.98
Power loss
(at 2.5 kHz)
[kW]
0.11
0.12
0.16 0.16 0.24 0.36
Cooling-air requirement [m³/s]
0.009 0.009 0.009 0.022 0.022 0.028
Pressure drop
∆
p
[Pa]
10 10 10 32 32 30
Sound pressure levels, types of construction, dimensions, weights
Sound
pressure
level
[dB(A)]
60 60 60 60 60 60
Type
of
construction
A A A B B C
Dimensions [mm]
•
Width
•
Height
•
Depth
90
425
350
90
425
350
90
425
350
135
425
350
135
425
350
180
600
350
Weight approx.
[kg]
8.5 8.5 8.5 12.5 12.5 21
Table 13-5
Air-cooled converter (part 3)