05.2006
Connecting-up
Siemens AG
6SE7087-2JD60
SIMOVERT MASTERDRIVES
Operating Instructions
7-21
The following table shows how the existing line voltage is assigned for
adjustment by the fan transformer.
Rated
input
voltage
3 AC 200 V (- 15 %)
to 230 V (+ 15 %)
3 AC 380 V (- 15 %)
to 480 V (+ 10 %)
3 AC 500 V (- 15 %)
to 600 V (+ 10 %)
3 AC 660 V (- 15 %)
to 690 V (+ 15 %)
Supply
voltage
Transformer tappings
3 AC 170 V
200 V
3 AC 200 V
200 V
3 AC 220 V
220 V
3 AC 230 V
230 V
3 AC 264 V
230 V
3 AC 325 V
380 V
3 AC 380 V
380 V
3 AC 400 V
400 V
3 AC 415 V
400 V
3 AC 425 V
400 V
500 V
3 AC 440 V
440 V
500 V
3 AC 460 V
460 V
500 V
3 AC 480 V
460 V
500 V
3 AC 500 V
460 V
500 V
3 AC 525 V
460 V
525 V
3 AC 575 V
575 V
660 V
3 AC 600 V
575 V
660 V
3 AC 660 V
575 V
660 V
3 AC 690 V
690 V
3 AC 790 V
690 V
Table 7-10
Connecting the fan transformer
Connecting the fan
transformer