LOOPC
Loop current (PA)
CVOLT
Terminal voltage (PB)
Factory setting:
PRESS
Note
To have the process value for "Level", "Volume", "Mass flow", "Volume flow" or "Customized
characteristic curve" shown as the "Start view", first set the associated characteristic curve
using the "Application" (Page 106) parameter.
9.2.31
Pressure reference [33]
Used to adapt the display of the pressure unit to your application.
Setting range:
NONE
Not specified
GAUGE
Gauge pressure
ABS
Absolute pressure
Factory setting:
NONE
See also
Pressure units [01] (Page 101)
9.2.32
Identify the device [34]
Enables or disables the device identification via HART.
When device identification is enabled, the device signals its identification data via HART.
With device identification enabled, the device responds to a request with the HART command
"Find device".
Setting range:
ON
Device identification enabled
OFF Device identification disabled
Factory setting:
OFF
Parameter assignment
9.2 Parameter assignment over device with display
SITRANS P320/P420 (mA/HART)
Operating Instructions, 06/2018, A5E44852162-AA
139