Result
The User PIN is disabled.
9.2.26
Active device mode [28]
Shows the mode in which the device is operated.
The parameter is only visible for devices with Functional Safety.
Setting range:
STD
Functional Safety is disabled
FUNCT
Validation of the safety-related parameters and/or the fail-
safe behavior is performed
SAFE
Functional Safety is enabled
ERROR
Safety critical device error
O/S
Out of service mode, non-safe mode
Factory setting:
STD
See also
9.2.27
Functional Safety [29]
Enables Functional Safety.
The parameter is only visible for devices with Functional Safety.
See also
9.2.28
Display test [30]
Used to check that numbers, texts and symbols appear correctly on the display.
● To start the display test, press the button and select "START".
When the display test is complete, the message "COMPL" appears.
● To cancel the display test, press the button.
Parameter assignment
9.2 Parameter assignment over device with display
SITRANS P320/P420 (mA/HART)
136
Operating Instructions, 06/2018, A5E44852162-AA