Device status symbols
Display
– NAMUR NE 107
NAMUR
– HCF
SIMATIC PDM/PLC
Symbol
Device status
Priority *
Priority *
Symbol
Device status
Priority *
Failure
1
1
Maintenance
alarm
1
Cause: Output signal invalid due to fault in the field device or in the peripherals.
Measure: Maintenance is required immediately.
Maintenance
required
3
4
Maintenance
demanded
2
Cause:Output signal is still valid, but wear reserve is almost exhausted or a function will be limited soon.
Measure:Maintenance is recommend as soon as possible.
Maintenance
required
3
4
Maintenance
required
3
Cause: Output signal is still valid. A limited function has not been detected, but wear reserve is anticipated within the next
few weeks.
Measure: Maintenance of device should be planned.
Function test
2
2
Manual opera‐
tion
4
Cause: Output signal temporarily invalid (e.g. frozen) due to work being performed on the device.
Measure: Manual mode over HMI or disable the engineering system.
Function test
2
2
Simulation
mode
5
Cause: Output signal temporarily does not represent the process, because the output is based on a simulation.
Measure: Simulation mode over HMI or disable the engineering system or restart device.
Failure
1
1
Out of service
6
Cause: Output signal does not represent process value. Device mode is set to "Out of service".
Measure: Disable "Out of service" and enable normal operation.
Failure
1
1
(red)
Configuration
error
7
Cause: Output signal invalid due to parameter setting, connection error or configuration error in the HW.
Measure: Check hardware configuration of the device over HMI or engineering system.
Diagnostics and troubleshooting
12.1 Device status symbols
SITRANS P320/P420 (mA/HART)
182
Operating Instructions, 06/2018, A5E44852162-AA