7.2.5.1
Changing parameter values
Requirement
The button lock is disabled.
Disabling button lock (Page 131)
Procedure
1. Navigate to the parameter view (Page 71)
2. Select the desired parameter with the or button.
Use the button to confirm.
You are in the edit view.
3. Change the parameter value with the or button.
To navigate faster, keep the or button pressed.
4. Apply the change with the button.
Or, cancel the change with the button.
7.3
Remote operation
7.3.1
Requirements
You can operate the device using HART communication. The following is required for this
purpose:
● A handheld (e.g. FC475) or PC software such as SIMATIC PDM.
● A HART modem to connect a PC with the device or a lead to connect the handheld with
the device.
7.3.2
SIMATIC PDM
Overview
SIMATIC PDM (Process Device Manager) is a universal, multi-vendor tool for configuration,
parameter assignment, commissioning, diagnostics and maintenance of intelligent field
devices and field components. You can learn about retro-installations and obtain additional
information on SIMATIC PDM on the Internet at SIMATIC PDM (
SIMATIC PDM monitors the process values, alarms and status signals of the device. The
software enables the display, comparison, adjustment, testing and simulation of device data
and the setting of calibration and maintenance due dates.
Operating
7.3 Remote operation
SITRANS P320/P420 (mA/HART)
Operating Instructions, 06/2018, A5E44852162-AA
77