9.2.3.1
Set damping value
Procedure
1. Navigate to the parameter view.
Navigating in the views (Page 71)
2. Select the "Damping value" parameter.
3. Press the button.
4. Set the damping with the and buttons.
5. To set the damping in steps of 0.10 s, press and hold down the buttons.
6. Use the button to confirm.
Result
You have set the damping value.
9.2.4
Application [05]
You use the "Application" parameter to adjust the device for the following measuring tasks.
● Pressure measurement
● Level measurement
● Volume flow measurement
● Mass flow measurement
● Volume measurement
● Customized characteristic curve (only available via remote operation). (Page 146)
Characteristic curves
The device uses a linear characteristic curve for pressure and level measurements.
For volume and mass flow measurements, the device uses adjustable square root functions.
For volume measurement, the device uses the tank characteristic curves for various vessel
geometries.
In the "Customized characteristic curve" application, enter the breakpoints of the characteristic
curve using remote operation (e.g. SIMATIC PDM).
The set application acts directly on the current output:
Parameter assignment
9.2 Parameter assignment over device with display
SITRANS P320/P420 (mA/HART)
106