66
PBD-51041388
SITRANS LG250 - Operating Instructions
46201-EN-150424
Code
Text mes-
sage
Cause
Rectification
M504
Error on an
device inter-
face
– Hardware defect
– Exchanging the electronics
– Send instrument for repair
M505
no measured
value avail-
able
– Sensor does not detect an
echo during operation
– Check and correct instal-
lation and/or parameter
adjustment
– Process component or
probe contaminated or
defective
– Clean or exchange process
component or probe
M506
Installation/
Setup error
– Error during setup
– Check and correct instal-
lation and/or parameter
adjustment
– Check probe length
M507
Error in the
instrument
settings
– Error during setup
– Error when carrying out a
reset
– False signal suppression
faulty
– Carry out reset and repeat
setup
10.4 Rectify faults
The operator of the system is responsible for taking suitable meas-
ures to rectify faults.
The first measures to be taken are to check the output signal as well
as to evaluate the error messages via the display and adjustment
module. Further comprehensive diagnostics can be carried out on a
PC with the software PACTware and the suitable DTM. In many cases,
the causes can be determined this way and faults rectified.
Connect a handmultimeter in the suitable measuring range according
to the wiring plan. The following table describes possible errors in the
current signal and helps to remove them:
Error
Cause
Rectification
4 … 20 mA signal
not stable
Level fluctuations
Set damping according to the instru-
ment via the display and adjustment
module or PACTware/DTM
4 … 20 mA signal
missing
Electrical connec-
tion faulty
Check connection according to
chapter "
Connection steps
" and if
necessary, correct according to chap-
ter "
Wiring plan
"
Voltage supply
missing
Check cables for breaks; repair if nec-
essary
Operating voltage
too low or load re-
sistance too high
Check, adapt if necessary
Reaction when malfunc
-
tion occurs
Fault rectification
Check the 4 … 20 mA
signal