Enter the suitable distance value in m for the empty vessel (e.g.
distance from the flange to the probe end) corresponding to the per
-
centage value. The distance refers tot he sensor reference plane (seal
surface of the process fitting).
This menu item is only available if you have selected interface meas-
urement under the menu item "
Application
".
You can accept the adjustment of the level measurement also for the
interface measurement. If you select "Yes", the current setting will be
displayed.
If you have selected "
No
", you can enter the adjustment for the inter-
face separately. Enter the requested percentage value.
For the full vessel, enter the distance value in m matching the per-
centage value.
This menu item is only available if you have selected interface meas-
urement under the menu item "
Application
". If you have selected "
Yes
"
in the previous menu item (accept adjustment of the level measure-
ment), the current setting will be displayed.
If you have selected "
No
", you can enter the adjustment for the inter-
face measurement separately.
Setup - Max. adjustment -
Interface
Setup - Min. adjustment -
Interface