Remote operation
7.1 Operating via AMS Device Manager
SITRANS LR250 with FOUNDATION FIELDBUS
80
Operating Instructions, 09/2021, A5E32221411-AH
1.
The default for level values is percent: if you want to select units instead, go to
Configure/Setup > LTB > Setup > Sensor > Level Unit
, and select the desired unit.
2.
Go to
Configure/Setup > LTB > Setup > Sensor > PV (Volume/Level) Unit
, and select the
desired volume units.
3.
From the Vessel Shape tab of
Configure/Setup > LTB > Setup > Linearization
, select
Linearization Table
option in the Vessel Shape field.
4.
Click on the Breakpoints tab and enter values for level and volume breakpoints in table.
The values corresponding to 100% and 0% levels must be entered. The breakpoints can be
ordered from top to bottom, or the reverse.
After completing the above steps you will need to configure AIFB 1 and/or AIFB 2. [See
AIFB 1
(2.6.)
and
AIFB 2 (2.7.)
]
7.1.9.5
Signal processing
Signal Processing (LTB)
Note
For more detailed explanations of the parameters listed below see the pages referenced.