Parameter reference
SITRANS LR250 with FOUNDATION FIELDBUS
Operating Instructions, 09/2021, A5E32221411-AH
137
Before Auto False Echo Suppression
①
TVT Hover Level
④
echo marker
②
default TVT
⑤
material level
③
false echo
1.
Determine Auto False Echo Suppression Range. Measure the actual distance from the sensor
reference point to the material surface using a rope or tape measure.
2.
Subtract 0.5 m (20") from this distance, and use the resulting value.
After Auto False Echo Suppression
①
false echo
④
material level
②
learned TVT
⑤
default TVT
③
Auto False Echo Suppression Range
⑥
echo marker