Commissioning
6.2 Operating via the handheld programmer
SITRANS LR250 with FOUNDATION FIELDBUS
54
Operating Instructions, 09/2021, A5E32221411-AH
Key
Name
Function
Plus or minus
sign
Numeric
editing
Changes the sign of the entered value.
to
Numeral
Numeric
editing
Enters the corresponding character.
6.2.3.2
Quick Start Wizard via the handheld programmer_note
Note
•
A reset to factory defaults should be performed before running the Quick Start Wizard if
the device has been used in a previous application. See
Master Reset (4.1.)
.
•
The Quick Start wizard settings are inter-related and changes apply only after you select
Finish
in the Wizard Complete step.
•
Do not use the Quick Start wizard to modify parameters: see instead Parameter reference
(Page 120). (Perform customization for your application only after the Quick Start has
been completed).
•
Default settings in the parameter tables are indicated with an asterisk (*).
1. Quick Start
1.1. Quick Start Wiz
•
Point the programmer at the display from a maximum distance of 300 mm (1 ft), then
press
RIGHT arrow
to activate PROGRAM mode and open menu level 1.
•
Press
RIGHT arrow
twice to navigate to menu item 1.1 and open parameter view.
•
Press
RIGHT arrow
to open Edit mode or
DOWN arrow
to accept default values
and move directly to the next item.
•
To change a setting, scroll to the desired item or key in a new value.
•
After modifying a value, press
RIGHT arrow
to accept it and press
DOWN arrow
to
move to the next item.
•
Quick Start settings take effect only after you select
Finish.