Parameter lists
A.2 Output
SITRANS FUS080 transmitter
72
Operating Instructions, 07/2012, A5E03059912-02
Modbus
Address
Parameter
Default
value
Value range
Access
level
Description
40824
442 Pulse B direction
Reverse
Forward,
Reverse,
Forward net,
Reverse net.
R/W
Pulse output calculation on pure
forward flow or pure reverse flow -
or net flow for forward and reverse
pulse flow.
Valid if pulse output B is enabled
and pulse function selected
40825
443 Amount per pulse B
1.000000
(m
3
)
0.000001 ...
1000000000
R/W
Volume per pulse.
Valid if pulse output B is enabled
and pulse function selected
40827
444 Pulse width for pulse B
5 ms
5, 10, 20, 50,
100, 200, 500
ms
R/W
Pulse length when the pulse is
active.
Valid if pulse output B is enabled
and pulse function selected
Communication
For editing the communication settings, use PDM device menu "Communication Setting"
40833
591 Device Communication
Address
1
1 ... 247
Read
Meter has default address value 1
with selectable address up to 247
40834
592 Baudrate
4
0 ... 5
Read
Communication port speed
40835
593 Parity
0
0 ... 3
Read
Communication port parity
40836
594 Interframe space
35
35 ... 255
Read
Minimum space between two
messages (bytes x 10)
40837
595 Response delay
5
1 ... 50
Read
Minimum time from receiving a
request to its response
Data logger
40619
600 Log interval
Monthly
Daily, Weekly,
Monthly
R/W
Log interval
40620
601 Day of week, if weekly log Sunday
Monday to
Sunday
R/W
When log interval is set to weekly
logging, this parameter defines what
weekday the logging is performed.
Valid if weekly log interval is
activated
40621
602 Limit for too high
consumption
1E+09
-3.4E+38 ...
+3.4E+38
R/W
Limit for too low consumption during
current log interval. Based on
totalizer 1 and the selected unit
40623
603 Limit for too low
consumption
No
-3.4E+38 ...
+3.4E+38
R/W
Limit for too low consumption during
current log interval. Based on
totalizer 1 and the selected unit
22
604 Reset log
No, Yes
HW
key
Reset data logger
Periodic log Totalizer 1
40770
160 Next settling date
01-01-
2000
dd-mm-yyyy
R/W
Next settling date where actual
value of totalizer 1 is stored
40773
161 Latest settling date
01-01-
2000
dd-mm-yyyy
Read Latest settling date where value of
totalizer 1 was stored
40776
162 Latest totalizer 1 value
0
Read Latest stored value of totalizer 1