Commissioning
6.4 Commissioning via PDM
SITRANS FUS080 transmitter
32
Operating Instructions, 07/2012, A5E03059912-02
1.
Press push button within six seconds to reset the internal battery counter. The message
"accept" will appear.
2.
Press push button again within six seconds in order to reset the internal battery counter.
The battery indicator now shows full. If the push button is not pressed again, the battery
indicator will show "Low".
/
Figure 6-1
Reset internal battery counter
* Software version
6.4
Commissioning via PDM
SIMATIC PDM (Process Device Manager) is a software package for configuring,
parameterizing, commissioning, and maintaining field devices (e.g. transducers).
Among other features, SIMATIC PDM contains a simple process for monitoring process
values, interrupts and status/diagnosis signals of a field device.
Note
For instructions on installation and operation of SIMATIC PDM, refer to the SIMATIC PDM
Getting Started (included in the documentation package that comes with PDM).
Note
Minimum PDM version required is SIMATIC PDM V6.0 + SP5
Note
Default password
Any data changes in PDM requires a password. The default password is 1000. For further
information, see "Password-protected data" (Page 46).
In the following it is described how the device is commissioned using SIMATC PDM.