Safety, approvals, EMC
7.4 EMC
SITOP PSU8200/3800 3ph
Manual, 05.2018, C98130-A7638-A1-6-7629
89
7.4
EMC
6EP3436-8SB00-0AY0 (24 V/20 A)
6EP1437-3BA10 (24 V/40 A)
6EP3437-8SB00-0AY0 (24 V/40 A)
6EP3446-8SB10-0AY0 (36 V/13 A)
6EP3446-8SB00-0AY0 (48 V/10 A)
6EP3447-8SB00-0AY0 (48 V/20 A)
6EP3424-8UB00-0AY0 (12 V/20 A)
6EP3436-8UB00-0AY0 (24 V/17 A)
6EP3437-8UB00-0AY0 (24 V/40 A)
Electrostatic discharge
EN 61000-4-2
8 kV contact, 8 kV air
Electromagnetic fields
EN 61000-4-3
80 - 1000 MHz 25 V/m
1000 - 2700 MHz 10 V/m
High-speed transient disturbance
variables (burst)
EN 61000-4-4
4 kV at line supply connections
2 kV at the DC output
Surge voltages
EN 61000-4-5
3 kV symmetrical at the line connections
6 kV unsymmetrical at the line connections
500 V symmetrical/unsymmetrical at DCoutput cables
High-frequency fields
EN 61000-4-6
10 V; 0.15 - 80 MHz
Magnetic fields
EN 61000-4-8
30 A/m; 50 Hz
Emitted interference
EN 55022
Class B
Line harmonics limit
EN 61000-3-2
Class A
Generic standards
EN 61000-6-2
Noise immunity for industrial environments
EN 61000-6-3
Emission for residential areas